Technical data of the side control (s/hart), S/hart), Technical data (s/hart) – Burkert Type 8635 User Manual
Page 26

24 - 8635
S
YSTEM
D
ESCRIPTION
(S/HART)
OPERATING CONDITIONS
Permissible ambient temperature
-25 ... +65 °C (with non-Ex devices or T4/T5)
-25 ... +60 °C (with T6)
System of protection
IP 65 to EN 60529
(only with correctly connected cable)
CONFORMITY TO THE FOLLOWING STANDARDS
CE Symbol
Conformity wrt. EMC Guideline 89/336/EEC
Low Voltage Guidline
73/23/EEC
Explosion protection (optional)
EEX ia IIC T4/T5/T6
MECHANICAL DATA
Housing dimensions, outside (WxHxD)
174 x 88 x 93 mm
Housing material
Aluminium
hard anodized and plastic-coated
Seal material
NBR / Neoprene
Other exterior parts
stainless steel (V4A)
Mass
approx. 1.5 kg
ELECTRICAL DATA
Connections
2 M20x1.5 bushings
with screw terminals 0.14 ... 1.5 mm
2
Power supply
via setpoint input 4-20 mA
Burden voltage
< 12 V DC
Burden resistance
590
Ω at 20 mA and 11.8 V DC
Process value input (option)
4-20 mA
Burden voltage
200 mV at 20 mA
Burden resistance
10
Ω
Binary input
mechanical make/break contact
Inductive proximity switch (optional)
to DIN EN 60947-5-6 (NAMUR)
Structural shape
SJ3.5-G-N
Manufacturer
Pepperl+Fuchs
Output signal for
switching amplifier
to DIN EN 50227 (NAMUR)
Rated voltage U
0
8 V
Current (sensor uncoated)
≥
2.1 mA
Current (sensor coated)
≤
1.2 mA
Technical data of the SIDE Control (S/HART)
Technical data (S/HART)