Operation as a positioner (s/hart), S/hart) – Burkert Type 8635 User Manual
Page 19

8635 - 17
S
YSTEM
D
ESCRIPTION
(S/HART)
The SIDE Control
(S/HART controls the position of the pneumatic actuator, whereby the position sensor
measures the actual position (POS) of the actuator. The controller compares this actual value of the
position with the setpoint (CMD), which is presented as a standard signal. If a control difference (Xd1)
exists, a pulse-width modulated voltage signal is sent to the positioning system as the correcting variab-
le. If the difference is positive, the pressurizing piezoelectric valve is driven via output B1; if it is negative,
the exhausting piezoelectric valve is driven via output E1. In this way, the position of the actuator is
altered until the control difference is 0. Z1 represents a disturbance.
Operation as a positioner (S/HART)
Position sensor
Position
setpoint
Positioner
Positioning system
(piezoelectric valves)
Continuous
valve
Valve opening
Position control loop
- Type 0125 (15 pages)
- Type 0121 (4 pages)
- Type 0330 (2 pages)
- Type 0331 (4 pages)
- Type 6012 (4 pages)
- Type 0127 (18 pages)
- Type 0131 (5 pages)
- Type 0141 (5 pages)
- Type 0142 (12 pages)
- Type 0145 (3 pages)
- Type 0174 (5 pages)
- Type 0212 (2 pages)
- Type 0211 (5 pages)
- Type 0212-B (18 pages)
- Type 0250 (64 pages)
- Type 0253 (2 pages)
- Type 0355 (2 pages)
- Type 0255 (15 pages)
- Type 0255 (2 pages)
- Type 8640 (55 pages)
- Type 8640 (119 pages)
- Type 8006 (34 pages)
- Type 8640 (2 pages)
- Type 0256 (15 pages)
- Type 0256 (2 pages)
- Type 0258 (72 pages)
- Type 0262 (5 pages)
- Type 0273 (6 pages)
- Type 0280 (5 pages)
- Type 0280 (2 pages)
- Type 0280 (12 pages)
- Type 0281 (2 pages)
- Type 0282 (2 pages)
- Type 0283 (2 pages)
- Type 0286 (4 pages)
- Type 0287 (15 pages)
- Type 0290 (14 pages)
- Type 0290 (2 pages)
- Type 0293 (18 pages)
- Type 0300 (6 pages)
- Type 0301 (6 pages)
- Type 0311 (2 pages)
- Type 0312 (6 pages)
- Type 6519 (4 pages)
- Type 6519 (2 pages)