Operating mode manual, S/hart) displays in operating mode manual, Meaning of the keys in operating mode manual – Burkert Type 8635 User Manual
Page 109
8635 - 107
O
PERATING THE
P
ROCESS
C
ONTROLLER
(S/HART)
Displays in operating mode MANUAL
The last display set in the AUTOMATIC mode is shown.
By selecting
POS_XXX, the actual position of the valve actuator can be checked.
To dislay the actual position of the valve actuator during MANUAL operation, first change to the display
POS_XXX in the AUTOMATIC mode.
Operating mode MANUAL
In the MANUAL mode, the valve can be opened and closed by hand.
Meaning of the keys in operating mode MANUAL
Press the
key in the MANUAL mode:
actuator pressurized (SFA*: valve opens, SFB*: valve closes)
Press the
key in the MANUAL mode:
actuator vented (SFA*: valve closes, SFB*: valve opens)
Hold down the
key and simultaneously press the
key:
fast pressurization of actuator (SFA*: valve opens, SFB*: valve closes)
Hold down the
key and simultaneously press the
key:
fast venting of actuator (SFA*: valve closes, SFB*: valve opens)
*SFA: actuator closes by spring force
*SFB: actuator opens by spring force
+
+
MANUAL
mode
Valve closes
at normal
speed
AUTOMATIC
mode
No
operating
action
release
(> 5 Sek.)
Configuration
Menu item
Release key
Release key
Valve closes
fast
Valve opens
at normal
speed
Valve opens
fast
release
END