Burkert Type 8635 User Manual
Page 59

8635 - 57
O
PERATING AND
C
ONTROLLER
F
UNCTIONS
POS MIN
POS MAX
TUNE-END
TUNE-POS
A.LIM NO
A.LIM YES
EEPROM
POS-MAX
POS-MIN
EEPROM
TUNE-PWM
YB
XXX
YE
XXX
TUNE-AIR
T.OPN XX
T.CLS XX
X.TUNE
TUNE END
X.T XXX
TUNE 0
TUNE 1
TUNE 2
TUNE 3
TUNE 4
TUNE 5
AUTOTUNE
MANUAL TUNE
release
move to max.
position
move to min.
position
change min.PWM-T.V. for
pressurizing valve
change min. PWM-T.V. for
exhausting valve
Display of opening time (s)
Display of closing time (s)
MANUAL TUNE FUNCTIONS
Access to the manual
TUNE functions can be obtained by the selecting of X.TUNE in the main menu
and briefly pressing the MANUAL/AUTOMATIC key or aborting the countdown by releasing the MANU-
AL/AUTOMATIC key.
The following parameters, which are determined automatically during
X.TUNE , may be preset or
changed afterwards manually.
TUNE-END
- Return to main menu
TUNE-POS
- Preset end positions
The
AUTOTUNE function determines the end positions of the control armature automatically on the
basis of the physical stops. Certain armatures (e.g. continuously turning butterfly valves) possess no
physical end stop, so that the end positions must be manually preset by means of
TUNE-POS. An
immediately following
AUTOTUNE takes over the manual end position settings and continues with
setting the positioning system and optimization of the positioner.
NOTE
If a manual preset of the end positions with
TUNE-POS is necessary, it must be done
before execution of AUTOTUNE.
5 s
Countdo
wn