Entering Battery Mhos:
To enter the battery MHOS reading, press the
BATT softkey on the XM3 main menu. Next
select the BATT CONFIG sub-menu. Scroll the
screen using the arrow keys until BATT MHOS
appears at the top of the screen. Press the
ENTR softkey. The APP card will now take over
control of the display and show a list of installed
batteries.
B
ATT A1 MHOS
0M
BATT A2 MHOS
0M
BATT A3 MHOS
0M
ENTR
ESC
BATT A1 MHOS
0000M
ADJUST VALUE
ENTR TO SHIFT FIELD
ENTR
ESC
BATT A1 MHOS
1200
M
@ 75F / 24C = 1209
ENTR
ESC
Use the softkeys to select the appropriate
battery.
To enter the MHOS value, press the ENTR
softkey. The following screen will appear.
Use the arrow keys to select the flashing digit
value. Press the ENTR softkey to move to
the next digit, and so on. When all digits have
been entered, the units will flash. The display
will show the entered mhos value and the
temperature compensated value. The PTS
probe temperature is used for temperature
compensation.
Press the ENTR softkey one more time to save
the value.
Only the temperature compensated value will be
logged or displayed from this point forward.