0 maintenance – Alpha Technologies XM3-HP Series - Technical Manual User Manual
Page 103

103
017-882-B0-001 Rev. C2 (10/2013)
4.0
Maintenance
Parameter
Model Number
220 GOLD-HP
220GXL
195 GOLD-HP
195GXL
Terminal Type
Threaded Insert
Threaded Insert
Threaded Insert
Threaded Insert
Bolt Size
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
10-32 UNC Bolt
Annual Retorque Inch-Pounds / N•m
110In-lb / 12.4N•m 110In-lb / 12.4N•m 110In-lb / 12.4N•m 110In-lb / 12.4N•m
Open Circuit Voltage
12.84
12.84
12.84
12.84
Average Float Voltage Range (volts/unit)
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
20-Hour Ampere Rate to 1.75 V/C
5.45
5.45
5.00
5.00
Typical Impedance @ 60Hz ohms
0.0050
0.0050
0.0050
0.0050
Typical Conductance 7Hz mohs
960 to 1400
960 to 1400
880 to 1320
880 to 1320
Typical 10 Sec. Voltage @ 100 amp
11.4
11.4
11.3
11.3
Parameter
Model Number
195GXL FT
165GXL
135AGM-P
85GXL-HP
Terminal Type
16mm Insert
Threaded Insert
Threaded Insert
Threaded Insert
Bolt Size
M6 thread
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
10-32 UNC Bolt
Annual Retorque Inch-Pounds / N•m
110In-lb / 12.4N•m 110In-lb / 12.4N•m 110In-lb / 12.4N•m
25In-lb / 2.8N•m
Open Circuit Voltage
12.84
12.84
12.84
12.84
Average Float Voltage Range (volts/unit)
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
20-Hour Ampere Rate to 1.75 V/C
5.50
4.30
3.75
2.50
Typical Impedance @ 60Hz ohms
0.0050
0.0055
0.0055
0.0040
Typical Conductance 7Hz mohs
800 to 1200
800 to 1200
900 to 1350
480 to 720
Typical 10 Sec. Voltage @ 100 amp
10.8
11.2
11.2
11.6
4.4
Battery Maintenance, continued
4.4.6 Periodic Maintenance Tasks, continued
4.0
Maintenance, continued
4.4.6.2 On-Site Battery Preventive Maintenance, continued
Parameter
Model Number
3.5 HP
4.0 HP
Terminal Type
Threaded Insert
Threaded Insert
Bolt Size
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
Annual Retorque Inch-Pounds / N•m
110In-lb / 12.4N•m 110In-lb / 12.4N•m
Open Circuit Voltage
12.80
12.80
Average Float Voltage Range (volts/unit)
12.6 to 14.1
12.6 to 14.1
Typical Impedance @ 60Hz ohms
2.7
2.2
Typical Conductance 7Hz mohs
1400 to 1850
1700 to 2500
Table 4-1, On-Site Battery Preventive Maintenance