0 operation, Table 3-3, logged events and alarms – Alpha Technologies XM3-HP Series - Technical Manual User Manual
Page 72

72
017-882-B0-001 Rev. C2 (10/2013)
3.0
Operation
3.4.2 Applications, continued
Event Logging App:
The APP card has a 768 record event log. This log does roll-over when the maximum size has
been reached. When the roll-over occurs, the oldest 64 records are erased to make room for
new records. Once a roll-over has occurred, the number of records available will be between 704
and 768. See Table 3-3 for a list of Events and Alarms that are logged.
EL 02/06/12
08:38:33.00
MINOR ALARM: XM3-1
INPUT FAILURE=ALARM
ESC
This is an example event log screen shot. The
“EL” denotes the event log, and the record was
time stamped on February 6, 2012 at 8:38:33 in
the morning.
The up and down arrow keys step through the
log records forward and backward in time.
3.4
AlphaAPPs Overview, continued
3.0
Operation, continued
TABLE OF EVENTS/ALARMS LOGGED
ALPHADOC OPTION
DNSTRM POWER FAULT
OUTPUT 1 TRIPPED ALARM
APP CARD CODE DOWNLOADED
EVENT LOG CLEARED
OUTPUT 2 ENABLE
APP CARD HARDWARE STATUS
HIGH BATT VOLTS
OUTPUT 2 TRIPPED
APP CARD REAL TIME CLOCK SET
HIGH BATTERY ALARM
OUTPUT FAILED ALARM
APP CARD RESET CAUSE
HW COMPATIBILITY
OUTPUT FAILURE
APP CARD TECHNICIAN CODE ENTERED
INPUT FAILURE
OUTPUT OVERLOAD
APP OPTION
INPUT FAILURE ALARM
OUTPUT OVERLOAD ALARM
BATT TEMP PROBE
INPUT OVER CURR
PDB EEPROM ERROR
BATTERY EOD
INV EEPROM ERROR
POWER SUPPLY INPUT CURRENT LIMIT ALARM
BATTERY FAIL
INVERTER ALARM
REFRESH
BATTERY LOG CLEARED
INVERTER ALARM
SAG DELTA MEAN
BATT. TEMPERATURE PROBE STATUS ALARM
INVERTER ENABLE
SAG NO HARNESS
CHARGER ENABLE
INVERTER TEMP
SAG NOT CALIBRATED
CHARGER FAIL ALARM
LINE ISOLATION
SAG OPTION
CHARGER FAILURE
LINE ISOLATION ALARM
SAG RELAY STUCK
CLOCK NOT SET
LOW BATT VOLTS
SELF TEST ALARM
CM IP ADDRESS
LOW BATTERY SHUTDOWN ALARM
SELF TEST FAIL
CM MAC ADDRESS
MAJOR APPLICATION ALARM
SELF TEST FAIL ALARM
CONFIG ERROR
MINOR APPLICATION ALARM
STR X MISWIRED
CONFIGURATION LOG CLEARED
NO BATTERIES
SURGE MOV FAIL
CPE IP ADDRESS
OUTPUT 1 ENABLE
X BAL STAGE
CPE MAC ADDRESS
OUTPUT 1 TRIPPED
Table 3-3, Logged Events and Alarms