0 maintenance – Alpha Technologies XM3-HP Series - Technical Manual User Manual
Page 104

104
017-882-B0-001 Rev. C2 (10/2013)
4.0
Maintenance
4.4
Battery Maintenance, continued
4.4.7 Battery Refurbishment Plan
4.0
Maintenance, continued
Does battery meet
the minimum
conductance values
per Table 4-2?
Yes
Measure
Conductance
Measure
Battery
Voltage
Sort Batteries per
Conductance &
Voltage
Batteries Returned
from Site. Measure
and document 24
hour Open Circuit
Voltage (OCV).
(
Must occur within 24
hours of removal from
charger)
Properly recycle
batteries per EPA
requirements
Battery
Refurbishment
Plan
Group re-deployable
batteries as indicated for
future deployment as
strings
No
Yes
Does battery meet
the minimum of
12.6 Volts for the 24
hour OCV?
Measure
Battery
Voltage
Batteries stored in
warehouses for
extended periods of
time refer to
Section
4.4.3, Disposal,
Recycling and Storage
Instructions
No
Fig. 4-7, Flow Chart for Battery Refurbishment Plan
1.
DO NOT mix batteries of different models within in a string. Example: 165GXL with 195GXL.
2.
DO NOT mix batteries from different manufacturers. Example: Alpha and MK.
3.
No battery age limit if it passes the other tests.