0 maintenance – Alpha Technologies XM3-HP Series - Technical Manual User Manual
Page 101
101
017-882-B0-001 Rev. C2 (10/2013)
4.0
Maintenance
4.4
Battery Maintenance, continued
4.4.6 Periodic Maintenance Tasks, continued
4.0
Maintenance, continued
4.4.6.2 On-Site Battery Preventive Maintenance
Required Equipment
•
True RMS Volt Meter with DC Amp Clamp
•
Midtronics Conductance Battery Tester
Fig. 4-6, Flow Chart for Preventive Maintenance
Yes
No
Yes
Yes
No
Replace the individual failed battery with
a battery that is within +/- .3 Volts of the string average.
Battery String
Float Current
>0.5A
Log each battery’s
conductance and
voltage
Disconnect
Batteries
Record Information
on Site Visit Record
Monitor as per PM
Program
Site Visit
Battery
Refurbishment
Plan
Return battery to
warehouse
Remote Status
Monitoring
Procedure
Ensure Power
Supply is in Float
Mode
Battery
> 0.5V
from the average
string voltage
No
Does the individual battery pass
the Evaluation Procedure #1
outlined in Section 3.4?
(see page 18)
Replace the string
- AlphaCell GelCell Series (32 pages)
- FXM 650, 1100, 2000 UPS (96 pages)
- Cordex 48-1.2kW (68 pages)
- Radium MiniBay (57 pages)
- Fiber Backhaul Enclosure (FBE) (19 pages)
- FBE2322 Enclosure System (38 pages)
- FlexNet PMR, GMR Series (49 pages)
- Te25xh (38 pages)
- FlexNet MPS48-12M - Technical Manual (33 pages)
- FlexNet MPS48-12M - Quick Start Guide (2 pages)
- FlexNet ELPM 300-48D (25 pages)
- FlexNet FMPS (40 pages)
- FlexPoint AX Series (34 pages)
- FlexPoint FPR1207-F - Technical Manual (18 pages)
- FlexPoint FPR1207-F - Quick Start Guide (2 pages)
- AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual (79 pages)
- AlphaGen CE-3x2 5K-T 48Vdc (95 pages)
- AlphaGen PN-6x-T 7.5kW 48Vdc (95 pages)
- AlphaGen 3.5_5.0kW Kohler COM5 (80 pages)
- Security Bar Field For UPE-3, UPE-6, UPE-M3, UPE-M6, PN Series and CE Series (2 pages)
- AMPS80 HP (116 pages)
- 255A Bypass Switch (24 pages)
- AMP24 HP (108 pages)
- FXM350_Micro350 UPS (112 pages)
- CFR 600, CFR 600XT, CFR 1000 (70 pages)
- BPS Series Bypass Switch (36 pages)
- CFR Intelligent Interface Device (54 pages)
- CFR Redundant Control Unit (23 pages)
- CFR 5000, CFR 5000RM (88 pages)
- CFR 3000, CFR 3000RM (86 pages)
- CFR 1500, CFR 1500RM (83 pages)
- CFR 1500, CFR 2000, CFR 2500, CFR 3000 (76 pages)
- Continuity: 1000_2000_3000 (48 pages)
- Continuity Battery Pack (20 pages)
- Continuity: 6K_10K (52 pages)
- Micro, Micro XL, Micro XL3 UPS (99 pages)
- Micro Secure UPS (80 pages)
- Te17 (32 pages)
- Te45 (68 pages)
- Te41, 48V (76 pages)
- Te41, 24V (72 pages)
- Te43 (60 pages)
- AlphaGuard AG-CMT Installation (2 pages)
- AlphaGuard AG-CMT-3SC_4SC-P (2 pages)
- Digital Midtron DM-3200 AT (2 pages)