Tank Leak Test Menu

N = Tanks 1 – 8

(only the number of tanks programmed in

the System menu will appear)

Setup the confidence percentage

CONFIDENC

Press

M1

key.

LEAK TEST CONFIDENCE

99.0(%)

Use

UP/DOWN

keys to show choices.

90.0%

Press

ENTER

to accept this data.

95.0%
97.5%

Setup the percision of the leak test

PRECISION

Press

M2

key.

LEAK TEST PRECISION

Select tank number using (

M

) key.

TANK 1
TANK 2

:

TANK 8

(NOTE: 5 – 8 TS-2001/508 only)

LEAK TEST PRECISION
+0.20000

0.05 to 2.0

Use keypad to input a precision number.
Press

ENTER

to accept this data.

Setup a minimum amount of time to test for leaks per local regulations —

MIN LK TM

Press

M3

key.

MINIMUM LEAK TEST TIME

2

2 to 8.0 hours

Use keypad to input minimum leak test time.
Press

ENTER

to accept this data.

— Continued next page —

Monthly

Compliance

Yearly Test

Static Leak Test:

0.2 gph

0.1 gph

Precision Tank # 1

Precision Tank # 2

Precision Tank # 3

Precision Tank # 4

Precision Tank # 5

Precision Tank # 6

Precision Tank # 7

Precision Tank # 8

Threshold = 1/2 of Leak Test value