Cpm menu 19, Cpm menu notes: 19, Cpm menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual
Page 109

CPM Setup
Page
19 - 1
19
19
Cathodic Protection Monitor (CPM)
SETUP PROGRAMMING
CPM Menu
Remember:
The TS-CPM is programmed from the CPM
menu, which is under Setup. To reach this
menu, press the
Menu
key>
M1
then the
Down
t key until CPM is displayed.
Press the menu key (
M1
thru
M4
) that is below
the text: CPM. Two sub-menus are shown
under the Cathodic Protection Menu. Press
M1
to access the DATA menu and
M2
for the
ALARM menu.
Push
M1
under the DATA menu and select
ENABLE. Then select YES under the CPM
ENABLE menu, only when a CPM unit is/will be
attached to the Tank Sentinel tank gauge.
Press
M2
under the ALARM menu and select
AMPS.
CPM Menu Notes:
1) Before programming, reference the State and
Local Regulations about the interval of Cathodic
Protection Monitoring / Survey Reporting and
requirements.
2) Enter 80% of the output amperage level that
was documented on the last UST 3-6 Month(ly)
Survey Report and use this value as the current
limit (amp) alarm setpoint.
For Example: 80% of 4.2 amps = 3.36 (used for
the current alarm set-point)
Contents:
CPM Menu
Worksheet #19-1
Output Groups -
Line Leak Tests
See the Table of Contents to find topics in
this manual. See the Preface for general
information about this manual. And see the
Installation, Operator’s, TroubleShooting
Guides, and Application Notes for other
reference material.
SELECT MENU OPTION
(MORE)
S E T U P
UPGRADE LANGUAGE
DATALOG
M1
M2
M3
M4
Press the
DOWN
▼
key two or three times ...
SETUP MENU
(MORE)
EXIT
SYSTEM
TANKS
PROBES
H
U
MENU
×
Press this key and follow the
7
highlighted sequence below
—
CONTINUED
ON
NEXT
PAGE
—
CATHODIC PROTECTION
D ATA
ALARM
M1
M2
M3
M4
SETUP MENU
(MORE)
TS-ROM
SENSORS AUX INPUT
C P M
M1
M2
M3
M4