beautypg.com

Output groups, Output devices, Optionally – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

Page 13: Relays, Output modules, None ( no output group = default )

background image

PREFACE

Page

P - v

P

Programming Alarms, Limits, or Inputs to Output Groups

The TS-1001/504 / 2001/508 Tank Sentinels includes a powerful setup feature called –

Output Groups

(OGs). Alarms, limits, and inputs (Aux. or

I/O

Module inputs) can be

assigned / programmed to output groups (OUT GROUP or OG). An output device will turn
on or off when an alarm is active in any of its assigned output group(s). Up to 32 output
group(s) can be assigned or programmed to any output device... also see

Programming

Output Devices

.

The standard output devices are annunciators and relays. Other

output devices

can be

optionally

added to the system. These are

:

TS-ROM BriteBox

relays,

TS-CIM BriteBox

output modules

, and TS-IEM internal expansion PC Board

output modules

— for TS-2001/

508 consoles only.

Example:

TANK 1, ALARMS and the H LIM OG (high product level limit) menus:

The HIGH LIM (high product
level limit) has an associated H
LIM OG – high limit output
group near it.

In an 8 tank system
there are 8
H LIM OG s (one under
each tank menu).

Each limit, alarm or input can
be assigned to one of the 34
Output Group choices —
GROUP A thru FF, or to ALL
output GROUPS, or to

NONE

( no output group = default )

.

Record output group
assignments for each alarm,
limit, or input in theprovided
OG Worksheets.

Example

Output Group Assignment

WORKSHEET (partial)

HIGH PRODUCT OUTPUT GROUP 1

(UP/DN)

NONE

M1

M2

M3

M4

HIGH PRODUCT OUTPUT GROUP 1

(UP/DN)

GROUP A

M1

M2

M3

M4

HIGH PRODUCT OUTPUT GROUP 1

(UP/DN)

ALL GROUPS

M1

M2

M3

M4

NOTE

OG = Output Group

- Output Group Assignment WORKSHEET Output Group choices -

Example - System:

NONE = default setting (others are: GROUP A thru FF & ALL GROUPS)

NONE

LEAK OG

A

Tank Leak turns on Modulated Annunciator, Relay 2 for external leak light

A

THEFT OG

T

Sentinel Mode Theft Limit (turns on external product theft light)

B

SYSFL OG

F

System Fail - software or hardware failures - (activates solid annunciator)

C

E

F

Output Devices: Modulated Annunciator, Solid Annunciator, Relay 1, Relay 2,

I

/O Output Module

Channel # 1 to # __ (record all OG Assignments in the vertical column)

TANK ALARM 1

(MORE)

COPY

HIGH LIM

H LIM OG

HIGH HIGH

M1

M2

M3

M4