GE Industrial Solutions GE Zenith Series DPB User Manual
Page 89

81
Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
Series DPB Busway Installation & Operation Manual
The following Zero Current Registers set a bit for every channel, which reads a current that has gone to zero�
All alarms are active until reset by the controller, or the current returns to the channel� To reset any alarm,
read the register and then write the register with the desired alarm bit cleared�
Note: Current Loss is when the current goes above 1�5 Amps and then goes to zero an alarm is set for that
branch breaker� If bit 15 on the Current Option Setting is set the alarm will be active on the loss of current�
69�
R/W
NV
Zero
Current
Register
bit
0:
Breaker
1A
bit
1:
Breaker
1B
bit
2:
Breaker
1C
bit
3:
Breaker
2A
bit
4:
Breaker
2B
bit
5:
Breaker
2C
bits 6 – 15: Not Used Always read as 0
The following Warning Register sets a bit for every channel, which reads a current above the Warning
Threshold for at least the Warning Time-Delay� All warnings are latching and must be reset by the controller�
To reset any alarm, read the register and the write the register with the desired alarm bit cleared�
70�
R/W
NV
Warning
Register
(Latching)
bit
0:
Breaker
1A
bit
1:
Breaker
1B
bit
2:
Breaker
1C
bit
3:
Breaker
2A
bit
4:
Breaker
2B
bit
5:
Breaker
2C
bits 6 – 15: Not Used Always read as 0
The following Alarm Register sets a bit for every channel, which reads a current above the Alarm Threshold for
at least the Alarm Time-Delay� All alarms are latching and must be reset by the controller� To reset any alarm,
read the register and then write the register with the desired alarm bit cleared�
71�
R/W
NV
Alarm
Register
(Latching)
bit
0:
Breaker
1A
bit
1:
Breaker
1B
bit
2:
Breaker
1C
bit
3:
Breaker
2A
bit
4:
Breaker
2B
bit
5:
Breaker
2C
bits 6 – 15: Not Used Always read as 0
The following Warning Threshold register sets the thresholds for the Warning alarms� A Warning alarm
is given in percent of the breaker size registers for each phase (75 = 75%)� A Warning alarm will occur if
the measured current is above the Warning Threshold for at least the Warning Time Delay� Default for the
Warning thresholds is 70%� The Values that are written to the Warning Threshold must be between 40 and
100 and always below the corresponding Alarm Threshold�
72�
R/W
NV
Warning
Threshold
The following Alarm Threshold registers set the thresholds for the Alarms� A Alarm Threshold register
is given in percent of the breaker size registers for each phase (85 = 85%)� An Alarm will occur if the
Series