Series DPB Busway Installation & Operation Manual
BCMS Basic = Current Only
BCMS Plus = Current + Voltage
PERSONALIZATION
PARAMETER
DESCRIPTION
RESOLUTION
NOTES
BCMS
BASIC
BCMS
PLUS
Circuit Breaker Size:
Output circuit breaker rating
1 A.
Defines output circuit breaker ratings;
default is 20 A ; (20-100 A range)
a
a
Warning Time Delay:
Time (seconds) before warn-
ing alarm activates
0-60 seconds
Defines duration current must
exceed threshold before activating
a current warning alarm; default is 0
seconds
a
a
Alarm Time Delay:
Time (seconds) before alarm
activates
0-60 seconds
Defines duration current must
exceed threshold before activating
a high current alarm; default is 10
seconds
a
a
Demand Average Time:
Time (seconds) to
determine average current
1 second
Defines time by which average
current is determined; default is 15
seconds. Range is 15 - 60 seconds
a
a
Current Warning Alarm:
Circuit breaker current first
level alarm
40-100%
Defines threshold based on a
percentage of circuit breaker rating
(default is 70%) to activate current
warning alarm after a time delay
(default is zero seconds)
a
a
Current High Alarm:
Circuit breaker current
second level alarm
50-100%
Defines threshold based on a
percentage of circuit breaker rating
(default is 85%) to activate high cur-
rent alarm after a time delay (default
is 10 seconds)
a
a
Voltage Range:
Source voltage
0.1 V
Defines monitored voltage (208, 480,
600 VAC)
a
Frequency:
Source frequency
0.1 Hz
Defines frequency (60 Hz or 50 Hz)
a
Board Name Personal-
ization:
User defined device name
Alphanumeric
Device name; 16 Character maxi-
mum
a
Overvoltage Alarm:
High voltage detected on
source
0.1V
Defines voltage to activate over volt-
age alarm .(default is 200 VAC)
a
Undervoltage Alarm:
Low voltage detected on
source
0.1V
Defines voltage to activate under
voltage alarm (default is 60 VAC)
a