Mounting the end feed, Series dpb busway installation & operation manual, Figure 3a – GE Industrial Solutions GE Zenith Series DPB User Manual
Page 17: Figure 4a

9
Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
Series DPB Busway Installation & Operation Manual
MOUNTING THE END FEED
VERTICAL END FEED SUPPORT
Series DPB End Feed enclosures can be mounted in a number of ways. The recommended method for mounting Series DPB
End Feed enclosures is as shown in Figure 3. Four 3/8" threaded rods (see Figure 3A) secure the enclosure to the ceiling or to
Unistrut
TM
, and a standard busway hanger supports the Splice Extension. These need to be aligned and leveled to each other
so that the End Feed is completely level after installation.
HORIZONTAL END FEED SUPPORT
Series DPB End Feed enclosures can be horizontally mounted. The recommended method is similar to the vertical mounting
method and is shown in Figure 4 below. The enclosure is supported by four 3/8" threaded rods (see Figure 4A) secure the
enclosure to the ceiling or to Unistrut
TM
, and a standard busway hanger supports the Splice Extension. These need to be
aligned and leveled to each other so that the End Feed is completely level after installation.
UNISTRUT
TM
UNISTRUT
TM
THREADED ROD
THREADED ROD
END FEED
END FEED
VERTICAL BUSRAIL HANGER
HORIZONTAL BUSRAIL HANGER
END FEED OR
CEILING / UNISTRUT
TM
END FEED OR
CEILING / UNISTRUT
TM
Figure 3A
Figure 3 - Vertical End Feed Support
Figure 4A
Figure 4 - Horizontal End Feed Support
OPTIONAL BCMS
MONITORING MODULE
OPTIONAL BCMS
MONITORING MODULE
ON BOTTOM OF END FEED