17
Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
Series DPB Busway Installation & Operation Manual
INSTALLATION OF THE SPLICE CONNECTOR – 400 AMP
All busway sections will come from the factory with one splice connection.
As the busways section is mounted on its hanger supports, the abutting end of the splice section can be
installed to the adjoin busway section.
Connection of Busway Sections and Fittings: (See Figure 14)
1) Each section of busway will come with one Splice Pack assembly (D) and two "E" Clips (E) one at each
end of the bus section. Make sure the “E” Clips are always installed on each end of each rail.
2) Bus sections are phase-keyed to maintain proper circuit phasing of the run.
3) Section 2 (with the splice) and Section 1 (without splice) will be aligned on their respective supports.
Slide Section 1 forward on the splice pack.
4) Slide Splice Joint Covers (B & C) and "E" Clip (E) into place positioning them equally across the bus.
5) Slide Grounding Plate (A) into place and secure the four grounding screws to the busway. Tighten each
nut to a torque value of 85 in-lbs.
6) Slide the Splice Pack Assembly so that it is positioned equally on either side of the bus section joint.
7) See Figure 8 for Splice Installation reference. Starting from one end of the Splice Pack (Figure 15),
only use the steel cam-actuator tools supplied to expand the splice joint contact assemblies into
contact with bus sections bus bars.
i) Insert one tool into the first cam port #1; the second cam-actuator tool into the adjacent cam port
#2. Rotate each tool ¼ turn to expand the contact plates.
ii) Rotate the adjacent, non-metallic cam spacers (a & b), ¼ turn to hold the expanded contact plate
in place. DO NOT ATTEMPT TO USE THE NON-METALLIC CAMSPACERS TO EXPAND THE CONTACT
PLATE ASSEMBLIES.
iii) Rotate and remove the cam actuator tool in cam port #1, and insert it into cam port #3. Rotate the
steel tool in cam port #3, ¼ turn to expand the contact plates.
iv) Rotate the adjacent, non-metallic cam spacers (c & d), ¼ turn.
v) Rotate and remove the cam actuator tool in cam port #2, and insert it into cam port #4. Rotate
and remove the cam actuator tool in cam port #3, and insert it into cam port #5. Rotate the steel
tools in cam ports #4 and #5 to expand the contact plates.
vi) Rotate the adjacent, non-metallic cam spacers (e & f), ¼ turn.
diagram 7
A Top Grounding Plate
B Side Cover Support Plate
C Side Cover Support Plate
D Splice Pack Assembly
E “E” clip
1 Bus Section
2 Bus Section
A
E
E
B
C
D
Splice Pack
Grounding Stud Nut
Figure 14 - Splice Installation Overview - 400 Amp