Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
Series DPB Busway Installation & Operation Manual
If your voltage is between the limits, pick the Higher Limit�
13�
R/W
NV
Voltage Type (208, 380, 400, 415, 480, 600)
This register shows the setting for the Voltage monitoring setup� A set bit indicated active value�
14�
R/W
NV
Voltage
Option
Setting
bit
0:
Voltage
option
set
bit
1:
Set
for
50
Hz
bit
2:
External
LED
blink
bit
3:
Auto
Adjust
Gain�
bits 4 – 15: Not Used Always read as 0
These registers show the phase currents and are given in tenth of amps (100 = 10�0 Amps)
NOTE: If there are three two phase breakers, the center breaker’s current will be showed as Current, Breaker
1C & 2A.
15�
R/W
Current,
Breaker
1A
16�
R/W
Current,
Breaker
1B
17�
R/W
Current,
Breaker
1C
18�
R/W
Current,
Breaker
2A
19�
R/W
Current,
Breaker
2B
20�
R/W
Current,
Breaker
2C
21�
R
Current, Breakers 1A & 2A
22�
R
Current, Breakers 1B & 2B
23�
R
Current, Breakers 1C & 2C
These registers show the minimum phase currents and are in tenth of amps (100 = 10�0 Amps)� For three two
phase breakers, see Note on the Current Points above�
24�
R Minimum
Current,
Breaker
1A
25�
R Minimum
Current,
Breaker
1B
26�
R Minimum
Current,
Breaker
1C
27�
R Minimum
Current,
Breaker
2A
28�
R Minimum
Current,
Breaker
2B
29�
R Minimum
Current,
Breaker
2C
30�
R
Minimum Current, Breakers 1A & 2A
31�
R
Minimum Current, Breakers 1B & 2B
32�
R
Minimum Current, Breakers 1C & 2C
These registers show the maximum phase currents and are in tenth of amps (100 = 10�0 Amps)� For three
two phase breakers, see Note on the Current Points above�
33�
R Maximum
Current,
Breaker
1A
34�
R Maximum
Current,
Breaker
1B
35�
R Maximum
Current,
Breaker
1C
36�
R Maximum
Current,
Breaker
2A
37�
R Maximum
Current,
Breaker
2B
38�
R Maximum
Current,
Breaker
2C
39�
R
Maximum Current, Breakers 1A & 2A
40�
R
Maximum Current, Breakers 1B & 2B
41�
R
Maximum Current, Breakers 1C & 2C
Writing to this register will reset all Min and Max registers to currents present value�