Series DPB Busway Installation & Operation Manual
USING THE ACCUMULATOR SETUP PROGRAM
Main Window (See Figure 45):
Search – Will search for the Accumulator board� When you open the program it will automatically search for an
Accumulator board� If the search is successful “USB <-> Accumulator” should appear in the box beside the search button�
Open – This will open the connection to the Accumulator board� It will automatically open a connection on startup if the
Accumulator board is found�
Close – This will close the connection to the Accumulator board� It will automatically close the connection when the
program is closed�
Version – This is the version of the software in the Accumulator board� This may be helpful if you have issues and need to
contact GE for assistance�
Setup Tab:
The Setup tab is where most of the setup steps will be done� Pressing the
“Update” button on the right column will
update the data on this page�
At the top is the
Modbus setup� You can change the address, parity and baud rate� The addresses are sequential
starting with the base address� To change the address put the desired address in the box and press
“Set”� You will see
the addresses of the devices change in the list below� Use the pull-down box beside parity to change it� You can select
even, odd or none� Press
“Set” to set the parity� Use the pull- down box beside baud to change it� You can select 9600 or
19200� Press
“Set” to set the parity�
Figure 45 - BCMS Setup Tab
Search
Open
Version
Close
Update
Find Devices
Add
Remove
Swap
Reserve
Insert
Selected On
All Off
Default