GE Industrial Solutions GE Zenith Series DPB User Manual
Page 88

80
Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
Series DPB Busway Installation & Operation Manual
42�
W
Min/Max
Reset
The following Breaker Size Registers set the capacity of each breaker for the alarms� Units are in Amps (20
= 20 Amps)� The values that can be written are between 15 and 100� The Default value is -1 (65535)� If the
breaker is -1 (65535) then no alarm for this breaker will be given� This can be done by giving the breaker a size
0� For three two phase breakers, see Note on the Current Points above�
43�
R/W
NV
Breaker
Size
1A
44�
R/W
NV
Breaker
Size
1B
45�
R/W
NV
Breaker
Size
1C
46�
R/W
NV
Breaker
Size
2A
47�
R/W
NV
Breaker
Size
2B
48�
R/W
NV
Breaker
Size
2C
Writing to this register will set all the Breakers size registers to the value written� The Values that are written
to the Breaker sizes must be either zero or between 15 and 100� To remove all breakers, give a value of 0� This
register should always read 0�
49�
W
Global
Breaker
Size
These registers show current demand per phase and are in tenth of amps (260 = 26�0 Amps)� Values are the
average current over the time given in the Demand Register�
50�
R Demand
phase
1A
51�
R Demand
phase
1B
52�
R Demand
phase
1C
53�
R Demand
phase
2A
54�
R Demand
phase
2B
55�
R Demand
phase
2C
The Demand Register is time that the demand is averaged over in minutes� It must be between 15 to 60
minutes� The Default is 15 minutes�
56�
R/W
NV
Demand
time
These registers show Percent load and is given in tenth of a percent (753 = 75�3%)� These percents are the
Amps per phase divided by the breaker size of the same phase�
57�
R Percent
load
Breaker
1A
58�
R Percent
load
Breaker
1B
59�
R Percent
load
Breaker
1C
60�
R Percent
load
Breaker
2A
61�
R Percent
load
Breaker
2B
62�
R Percent
load
Breaker
2C
These registers show crest factor per phase� Values are peak current/rms current with three decimal places
(1412 = 1�412)�
63�
R Crest
Factor
Breaker
1A
64�
R Crest
Factor
Breaker
1B
65�
R Crest
Factor
Breaker
1C
66�
R Crest
Factor
Breaker
2A
67�
R Crest
Factor
Breaker
2B
68�
R Crest
Factor
Breaker
2C