beautypg.com

Toshiba – Toshiba Adjustable Speed Drive H3 User Manual

Page 88

background image

TOSHIBA

9 - 19

Parameter Explanations (cont'd)

Item 167,

LOW CURRENT DETECT LEVEL

- Enter the current amount (in % or amps depending on setting

of Item 296) below which the drive will trip and/or close an appropriately-programmed output contact.

Item 168,

LOW CURRENT DETECTION TIME

- Enter the time the output current must be below the

amount set in Item 167 before the drive trips and/or closes an appropriately-programmed output contact.

Item 169,

OUTPUT SHORT-CIRCUIT DETECTION SELECT

- To protect itself, the drive does an output

short-circuit check every time a run is initiated. This parameter changes the short-circuit check:

0: Standard setting
1: When a low impedance motor is used, this setting desensitizes the short-circuit check,
reducing nusiance trips.
2: This setting programs the drive to perform the check at power up only.
3: Combination of 1 and 2 above.
Do not operate the drive on a motor with power factor correction capacitors.

Item 170,

OVERTORQUE TRIP SELECTION

- Enter a "1" here to program the drive to fault

OVERTORQUE

TRIP

based on on the torque current amount. See Item 171.

Item 171,

OVERTORQUE TRIP LEVEL

- Enter the torque current (in % or amps depending on the setting

of Item 296,

CURRENT UNITS SELECTION

) at which the drive trips and/or closes an appropriately-

programmed output contact (see Items 60,63, or 66 and setting values 28/29 on page 9-11).

Item 172,

FAULT TRIP SAVING

- This parameter determines the effect of cycling power on a faulted

drive:

0: Fault and fault data cleared when drive powers up.
1: Drive powers up in tripped state (drive display remains in faulted state, but fault data and fault
contact are not maintained).

The setting of Item 153,

NUMBER OF RETRY ATTEMPTS

, is ignored by the drive when Item 172 is

set to "1".

Item 173,

COOLING FAN CONTROL SELECTION -

This parameter determines if the drive's fan is

thermostatically-controlled or if it runs continuously.

Item 174,

CUMULATIVE RUN TIMER ALARM SETTING -

One of the drive's output contacts can be

programmed to change state based upon the time entered here. See Items 60,63, or 66 and setting values

56/57 on page 9-12. ".01" is one hour.

PATTERN RUN

The H3 has a feature called pattern run that emulates a low-level PLC. During a pattern run, the drive
follows a

pattern group by running at the user's preset speeds for desired amounts of time in desired

directions with desired accel/decel times for a defined number of cycles. The H3 has 15 preset speeds,
any of which can be assigned to be speeds zero through seven in a pattern group. The drive can hold up
to four separate pattern groups, any of which can be remotely selected to run.

Item 175,

PATTERN RUN SELECTION -

This parameter enables pattern run. When stopping/starting

drive from panel, pattern run takes priority over the keypad's frequency reference.

Item 176,

PATTERN RUN CONTINUE MODE -

This parameter determines if a pattern group is continued

after a pattern run is stopped and restarted:

0: Pattern group starts over with its first speed
1: Pattern resumes at the time of and with the speed at interruption