beautypg.com

Toshiba, Group:terminal selection parameters – Toshiba Adjustable Speed Drive H3 User Manual

Page 41

background image

TOSHIBA

"LOW" CONTACTS

63

assign function to "LOW"

0 - 63

1

4

9-10

FUNCTION

contact

5-1

"LOW" CONTACTS

64

"LOW" output contact

1 - 100

1

1

9-10

DELAY TIME

delay time

5-1

"LOW" CONTACTS

65

"LOW" output contact

1 - 100

1

1

9-10

HOLD TIME

hold time

5-1

"FL" CONTACTS

66

asssign function to "FL" output

0 - 63

1

10

9-10

FUNCTION

contact

5-1

"FL" CONTACTS

67

"FL" output contacts

1 - 100

1

1

9-10

DELAY TIME

delay time

5-1

"FL" CONTACTS

68

"FL" output contacts

1 - 100

1

1

9-10

HOLD TIME

hold time

5-1

"OUT" CONTACTS

69

assign function to "OUT"

0 - 61

1

8

9-10

FUNCTION

output contacts

(available on option board)

"OUT" CONTACTS

70

"OUT" output contact delay time

1 - 100

1

1

9-10

DELAY TIME

(available on option board)

"OUT" CONTACTS

71

"OUT" output contact hold time

1 - 100

1

1

9-10

HOLD TIME

(available on option board)

LOW SPEED SIGNAL

72

Low-speed signal frequency

0 - Max. Output Freq. 0.1/0.01 Hz

0.0

9-13

OUTPUT FREQ

ACC/DEC COMPLETE

73

Acc/Dec complete detection

0 - Max. Output Freq. 0.1/0.01 Hz

2.5

9-13

DETECT BAND

bandwidth

SPEED REACH MAXIMUM

74

Speed reach high frequency

0 - Max. Output Freq. 0.1/0.01 Hz

0.0

9-13

FREQUENCY

SPEED REACH MINIMUM

75

Speed reach low frequency

0 - Max. Output Freq. 0.1/0.01 Hz

0.0

9-13

FREQUENCY

COMMERCIAL POWER/INV

76

Bypass control

0: Off

-

0

9-13

SWITCHING OUTPUT

1: Automatic

switching upon trip

2: Switching upon

receipt of
switching
signal *

3: Both 1 and 2

above*

COMMERCIAL POWER/INV

77*

Incoming power/inverter

0 - Max Output Freq

0.1/0.01 Hz 60.0 Hz

9-13

SWITCH FREQ

switching frequency

8 - 6

GROUP:TERMINAL SELECTION PARAMETERS

(cont'd)

PARAMETER

DESCRIPTION

LIQUID CRYSTAL DISPLAY

ADJUSTMENT

RANGE

ITEM

NO.

PAGE

NO.

DISPLAY

RESOLUTION

FACTORY

SETTING

Table continued on next page

*Item 77 is available only when Item 76 Adjustment Range option 2 or 3 is selected.

Specifications

Precautions

Wiring

Jumpers

Panel

Keypad

Parameters

Programming

Service

Dimensions

Index

Inspection