Toshiba, Group:special control parameters – Toshiba Adjustable Speed Drive H3 User Manual
Page 39
TOSHIBA
8 - 4
GROUP:SPECIAL CONTROL PARAMETERS
PARAMETER
DESCRIPTION
LIQUID CRYSTAL DISPLAY
ADJUSTMENT
RANGE
ITEM
NO.
PAGE
NO.
DISPLAY
RESOLUTION
FACTORY
SETTING
START-UP FREQUENCY
31
Start-up frequency
0.0 - 10
0.1/0.01 Hz
0.1
9-6
END FREQUENCY
32
End frequency
0.0 - 30
0.1/0.01 Hz
0.1
9-6
RUN FREQUENCY
33
Run frequency
0.0 - max output freq
0.1/0.01 Hz
0.0
9-6
RUN FREQUENCY
34
Run frequency hysteresis
0.0 - 30
0.1/0.01 Hz
0.0
9-6
HYSTERESIS
ENABLE JUMP
35
Jump frequency enable
0: Function OFF
-
0
9-6
FREQUENCIES
1: Function ON *
JUMP FREQUENCY #1
36*
Jump frequency #1
0.0-Max Output Freq
0.1/0.01 Hz
0.0
9-6
JUMP FREQUENCY #1
37*
+/- band # 1
0 - 30
0.1/0.01 Hz
0.0
9-7
BANDWIDTH
JUMP FREQUENCY #2
38*
Jump frequency #2
0.0-Max Output Freq
0.1/0.01 Hz
0.0
9-7
JUMP FREQUENCY #2
39*
+/- band # 2
0 - 30
0.1/0.01 Hz
0.0
9-7
BANDWIDTH
JUMP FREQUENCY #3
40*
Jump frequency #3
0.0-Max Output Freq
0.1/0.01 Hz
0.0
9-7
JUMP FREQUENCY #3
41*
+/- band # 3
0 - 30
0.1/0.01 Hz
0.0
9-7
BANDWIDTH
PWM CARRIER
42
PWM carrier frequency for 230V
500 Hz - 10 kHz
0.1kHz
2.2 kHz
9-7
FREQUENCY
(.75-30 HP)
PWM carrier frequency for 460V
500 Hz - 10 kHz
(1-125 HP)
PWM carrier frequency for 460V
500 Hz - 5 kHz
(125-300 HP)
*Items 36 - 41 are available only when Item 35 Adjustment Range option 1 is selected.
Specifications
Precautions
Wiring
Jumpers
Panel
Keypad
Parameters
Programming
Service
Dimensions
Index
Inspection