beautypg.com

Toshiba – Toshiba Adjustable Speed Drive H3 User Manual

Page 14

background image

TOSHIBA

3 - 1

NOTES:

1) NEMA Type1 UL/CUL listing

H3

STANDARD RATINGS

RATED

MOTOR

OUTPUT

OUTPUT

OVERLOAD

MAIN CIRCUIT

INPUT

KVA

HP(KW) CURRENT

VOLTAGE

CURRENT

INPUT POWER

CONTROL

(AMPS)

3-PHASE

POWER

2035

(1)

3.5

3/2.2

10.6

200-230V

120% FOR

200V/50Hz or

NO EXTERNAL

2055

(1)

5.5

5/3.7

17

3-PHASE

60 SEC.

200-230V/60Hz

CONTROL

2080

(1)

8

7.5/5.5

24.3

MAX VOLTAGE

110%

VOLTAGE +/- 10%

POWER SOURCE

2110

(1)

11

10/7.5

33

CONTINUOUS

FREQ. +/- 2Hz

REQUIRED

2160

(1)

16

15/11

46

2220

(1)

22

20/15

60

2270

(1)

27

25/18

75

2330

(1)

33

30/23

89

SECTION 3: Specifications

MODEL

NOTES

(see below)

MODEL

NOTES

H3

(see below)

STANDARD RATINGS

460 Volt NEMA Type 1 Chassis Standard Ratings

230 Volt NEMA Type 1 Chassis Standard Ratings

RATED

MOTOR

OUTPUT

OUTPUT

OVERLOAD

MAIN CIRCUIT

INPUT

KVA

HP(KW) CURRENT

VOLTAGE

CURRENT

INPUT POWER

CONTROL

(AMPS)

3-PHASE

POWER

4055

(1)

5.5

5/3.7

7.6

380-460V

120% FOR

380V/50Hz or

NO EXTERNAL

4080

(1)

8

7.5/5.5

11

3-PHASE

60 SEC.

400-460V/60Hz

CONTROL

4110

(1)

11

10/7.5

15

MAX VOLTAGE

110%

VOLTAGE +/- 10%

POWER SOURCE

4160

(1)

16

15/11

22

CONTINUOUS

FREQ. +/- 2Hz

REQUIRED

4220

(1)

22

20/15

28

4270

(1)

27

25/18.5

34

4330

(1)

33

30/22

40

4400

(1)

40

40/30

56

4500

(2)

50

50/37

65

4600

(2)

60

60/45

82

4750

(1)

75

75/55

104

410K

(1)

100

100/75

124

412K

(1)

125

125/90

156

415K

(1)

150

150/110

180

420K

(1)

200

200/150

240

425K

(1)

250

250/185

300

430K

(1)

300

300/220

360

NOTES:

1) NEMA Type 1 UL/CUL listing.