TOSHIBA

9 - 2

Blinding

To make the H3's many parameters more manageable, Toshiba employs "blinded" parameters
and "blinded" groups.

BLINDED PARAMETERS
Item 9,

VOLTAGE BOOST #1

, is an example of a "blinded" parameter. A blinded parameter is

identified in the parameter charts (which start on page 8-1) by its gray shading. A "blinded"
parameter is preceded by a parameter that has a shaded choice in the Adjustment Range column
(like Item 8,

VOLTS PER HERTZ PATTERN

). Item 9,

VOLTAGE BOOST #1

, is visible to the

programmer only if item 8,

VOLTS PER HERTZ PATTERN

, is set to "1" or "2". Note how

Adjustment Range 1 and 2 are shaded to indicate this. There are many other blinded parameters
in the H3.

BLINDED GROUPS
Of the twenty groups in the H3, only three are accessible when the drive is programmed with
factory defaults. To adjust a parameter that is not in one of the three visible groups, that
parameter's group must first be added to the group list. This is done in

GROUP: UTILITY

PARAMETERS

, which is one of the visible groups.

Programming Example 2

Objective: Change

ELECTRONIC THERMAL PROTECT LEVEL 1

in

GROUP: PROTECTION

PARAMETERS

to 89%.

Note 1:

ELECTRONIC THERMAL PROTECT LEVEL 1

is in a group that is not one of the three

groups visible when the drive is programmed with factory defaults. Therefore,

GROUP:

PROTECTION PARAMETERS

will have to be added to the visible group list.

Note 2:

GROUP: PROTECTION PARAMETERS

is added to the visible group list by changing item

304,

PROTECTION FUNCTION PARAMETERS BLIND

in

GROUP: UTILITY

PARAMETERS

to "1". To change item 304, however, it must first be unblinded by setting

Item 298,

BLIND FUNCTION SELECTION

in

GROUP: UTILITY PARAMETERS

to "1".

Step 1: Press PRG and use up arrow to display

GROUP: UTILITY PARAMETERS

. Press READ/

WRITE key. Drive will display

INDUSTRIAL APPLICATIONS

because it is the first

parameter in the group.

Step 2: Instead of using the down arrow to go through all the parameters in

GROUP: UTILITY

PARAMETERS

, use the up arrow to make the drive display the last visible parameter in

GROUP:UTILITY PARAMETERS

, which is item 298,

BLIND FUNCTION SELECTION

.

Step 3: Press READ/WRITE and adjust the "0" to a "1" using the arrow keys. Press READ/

WRITE again. Drive flashes

WRT

to confirm entry.

Step 4: Items 299-315 are now unblinded. Use the down arrow to display

PROTECTION

FUNCTION PARAMETERS BLIND

. Press READ/WRITE, use the up arrow to change the

"0" to a "1", and press READ/WRITE again. Drive flashes

WRT

to confirm entry.

Step 5: Press PRG twice to return to the group list. Use the arrows to verify that a fourth group,

GROUP:PROTECTION PARAMETERS

is now a part of the group list.

Step 6: Press READ/WRITE to enter the group. Drive will display Item 142,

DYNAMIC BRAKING

SELECTION

because that parameter is the first in the group.

Step 7: Use the down arrow to reach Item 158,

ELECTRONIC THERMAL PROTECT LEVEL 1

.

Step 8: Press READ/WRITE. Using the arrows, adjust the value to "89". Press READ/WRT. Drive

flashes

WRT

to confirm entry.

Step 9: Press PRG to leave programming.

Search Function

When

GROUP: PARAMETERS CHANGED FROM FACTORY DEFAULT

is displayed and READ/

WRITE is pressed, the drive will display

SEARCHING

. Any displayed parameters have been

changed to a value different from Toshiba's default. Press READ/WRITE to see the value of the
parameter. The parameter can be modified with the up/down arrows. Pressing READ/WRITE
again resumes the drive's search.