beautypg.com

Toshiba – Toshiba Adjustable Speed Drive H3 User Manual

Page 33

background image

TOSHIBA

7 - 2

PROGRAMMING MODE

Pressing the PRG button allows users to enter the programming mode. See parameter tree on

page 8-33 and parameter charts starting on page 8-1. Parameter explanations and examples can

be found in section 9.

LOCAL MODE: COAST STOP

In LOCAL mode, the drive's stop method can be changed to let the motor coast with the following

keystrokes.

Keystroke

Display

Comment

OUTPUT FREQUENCY

Standard output frequency display

60.0 HZ

LOCAL/REMOTE

COAST STOP COMMAND

Drive prompts user for coast stop command

(PRESS STOP)

STOP/CLEAR

OUTPUT FREQUENCY

Drive immediately stops firing transistors and motor

0.0 HZ

coasts to a stop

REMOTE MODE

The drive operates in REMOTE mode when the LOCAL/REMOTE LED is not illuminated. The
LOCAL/REMOTE LED can be turned on and off with the LOCAL/REMOTE key only when the
drive is stopped and at 0.0 Hz. With default programming, the drive powers up in remote mode. In
the remote mode, the drive is stopped/started remotely (e.g. from the terminal strip). To initiate a
run, the drive must have:

1. Drive enable ( e.g. "ST"-"CC" made)
2. Frequency command ( e.g. analog input to "IV", "RR", or other termials)
3. Direction command ( e.g. "R"-"CC" closure or "F"-"CC" closure )

See pages 5-2 and 4-1 for information on physical connections to the drive. See Items 44-55
on page 8-5 for information on the functions available using the input terminals. See Item 281,

COMMAND MODE SELECTION

and Item 282,

FREQUENCY MODE SELECTION

for information on

how to set where the drive receives start/stop and frequency commands.

REMOTE MODE: EMERGENCY OFF

EMERGENCY OFF can be executed from the keypad when running and operating in remote
mode. EMERGENCY OFF is stored as a past fault in the monitor, but does not change the state
of any "fault" contacts. When running in remote mode, press STOP/CLEAR twice to initiate an
EMERGENCY OFF command. Drive will stop motor according to method selected in Item 151,

EMERGENCY OFF MODE SELECTION

.

OTHER KEYPAD FUNCTIONS: LANGUAGE SELECTION

To change languages, press LOCAL/REMOTE + MON + PRG together with the display
showing

OUTPUT FREQUENCY

. Use the arrows to select the desired language and press WRT

to enter. As of 8/97, English and German are supported. German is available on the version 121
keypad ROM. To check keypad ROM number, press and hold the PRG button after pressing the
three buttons together as mentioned above. If drive displays "79", the keypad ROM is version 121;
if the drive displays "6E", the keypad ROM version is 110. If the drive does nothing, keypad ROM
is version 100.

Specifications

Precautions

Wiring

Jumpers

Panel

Keypad

Parameters

Programming

Service

Dimensions

Index

Inspection