beautypg.com

Toshiba – Toshiba Adjustable Speed Drive H3 User Manual

Page 70

background image

TOSHIBA

9 - 1

SECTION 9: Programming

Note: The H3 will "kick out" of programming mode (return to

OUTPUT FREQUENCY

display) when a

parameter name is displayed for fourteen seconds after the previous parameter has been read and
written.

Press the PRG button to access the H3's programming mode. The drive now displays the first of the
available groups.

The H3 parameters that have related functions are gathered into families called groups.

Use the up/down arrows to scroll through the available group list.

Groups

With factory default programming, the H3 displays only three groups:

GROUP: PARAMETERS CHANGED FROM FACTORY DEFAULT

GROUP: FUNDAMENTAL PARAMETERS #1

GROUP: UTILITY PARAMETERS

The following is a list of all H3 groups:

GROUP: PARAMETERS CHANGED FROM FACTORY DEFAULT

GROUP: FUNDAMENTAL PARAMETERS #1

GROUP: FUNDAMENTAL PARAMETERS #2

GROUP: PANEL CONTROL PARAMETERS

GROUP: SPECIAL CONTROL PARAMETERS

GROUP: TERMINAL SELECTION PARAMETERS

GROUP: FREQUENCY SETTING PARAMETERS

GROUP: PROTECTION PARAMETERS

GROUP: PATTERN RUN CONTROL PARAMETERS

GROUP: FEEDBACK PARAMETERS

GROUP: COMMUNICATION SETTING PARAMETERS

GROUP: INDUSTRIAL APPLICATION PARAMETERS (PUMP)

GROUP: INDUSTRIAL APPLICATION PARAMETERS (FAN)

GROUP: INDUSTRIAL APPLICATION PARAMETERS (CONVEYOR)

GROUP: INDUSTRIAL APPLICATION PARAMETERS (HOIST)

GROUP: INDUSTRIAL APPLICATION PARAMETERS (TEXTILES)

GROUP: INDUSTRIAL APPLICATION PARAMETERS (MACHINE TOOLS)

GROUP: AM/FM TERMINAL ADJUSTMENT PARAMETERS

GROUP: UTILITY PARAMETERS

GROUP: MOTOR PARAMETERS

Programming Example 1

Objective: Set

ACCELERATION TIME #1

to 23.4 seconds.

Step 1:

ACCELERATION TIME #1

(Item 10) is in

GROUP: FUNDAMENTAL PARAMETERS #1

,

so press the PRG key and use the up/down arrows to scroll through the group list until

GROUP: FUNDAMENTAL PARAMETERS #1

is displayed.

Step 2: Press the READ/WRITE key. Drive will then display

MAXIMUM OUTPUT FREQUENCY

(Item 1), because

MAXIMUM OUTPUT FREQUENCY

is the first parameter in

GROUP: FUNDAMENTAL PARAMETERS #1

.

Step 3: Use the up/down arrows to scroll through the parameters in

GROUP: FUNDAMENTAL

PARAMETERS #1

until the desired parameter (in this case,

ACCELERATION TIME #1

),

is displayed.

Step 4: Press the READ/WRITE key. Drive will display the value stored in this parameter.
Step 5: Adjust displayed value with up/down arrow keys. Press READ/WRITE when finished.

Drive flashes

WRT

to confirm entry.

Step 6: Use up/down arrows to select another parameter in this group, or press PRG to exit.