beautypg.com

Toshiba – Toshiba Adjustable Speed Drive H3 User Manual

Page 78

background image

TOSHIBA

9 - 9

Parameter Explanations (cont'd)

The following are the functions that are realized when the appropriate drive terminal is shorted to "CC".
Program the desired code from the list below into items 44-55 (see). Contact the factory on how to
make a function active when the terminal is disconnected from "CC" (fail-safe).

Code

Function

0

Reverse direction command (default for "R" terminal function)

1

Binary coding for number of preset speed desired. Value: +1 (default for "S1" terminal function)

2

Binary coding for number of preset speed desired. Value: +2 (default for "S2" terminal function)

3

Binary coding for number of preset speed desired. Value: +4 (default for "S3" terminal function)

4

Binary coding for number of preset speed desired. Value: +8 (default for "S4" terminal function)

5

Forward direction command (default for "F" terminal function)

6

Reset faults (momentary falling-edge trigger) (default for "RES" terminal function)

7

Drive enable (default for "ST" terminal function)

8

Jog (also need direction command). See items 108 and 109.

9

Select ACC1/DEC1 (open) or ACC2/DEC2 (closed to "CC")

10

Emergency stop. Also see item 151,

EMERGENCY OFF MODE SELECTION

.

11

DC injection. When outputting a frequency under

DC INJECTION START FREQUENCY

, short

terminal to "CC" to inject. Also see items 146, 147, and 148. Works in remote mode only.

12

Activate

GROUP:FUNDAMENTAL PARAMETERS #1

(open) or

GROUP:FUNDAMENTAL

PARAMETERS #2

(closed to "CC")

13

PID off (closed to "CC") or on (open)

14

Select Pattern Run #1

15

Select Pattern Run #2

16

Select Pattern Run #3

17

Select Pattern Run #4

18

Pattern Run continue signal

19

Pattern Run step signal

20

Jog forward (includes forward command). See items 108 and 109.

21

Jog reverse (includes reverse command). See items 108 and 109.

22

Bit #0 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/2048)

23

Bit #1 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/1024)

24

Bit #2 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/512)

25

Bit #3 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/256)

26

Bit #4 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/128)

27

Bit #5 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/64)

28

Bit #6 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/32)

29

Bit #7 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/16)

30

Bit #8 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/8)

31

Bit #9 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/4)

32

Bit #10 for binary speed reference (value of

MAXIMUM OUTPUT FREQUENCY

/2)

33

no function (use terminal to connect wires)

34

Motor operated pot: increase frequency reference

35

Motor operated pot: decrease frequency reference

36

Motor operated pot: clear frequency reference

37

Three wire control: NO momentary start push button

38

Three wire control: NO momentary stop push button. Contact factory for information on how to
realize stop with a NC contact.

40

Forward (open) or reverse (closed to "CC") command

41

Run (use in conjunction with 40 above)

42

Binary data write (use with 22-32 above). If no input terminal's function is set to "42", the drive
responds immediately to binary references commanded by changing data bits. If one of the input
terminal's function is set to "42", the drive responds to binary reference only when terminal is
closed to "CC". Binary reference is lost when power is cycled.

43

emulate LOCAL/REMOTE key

51

Drive/bypass switching signal

53

give "RR" priority over "IV" and "RX"

54

give "IV" priority over "RR" and "RX"