MONITOR MODE

Pressing the MON key switches the drive to monitor mode. The following table is an example of
the drive operation variables visible in the monitor:

The monitor has no effect on what is happening to the motor and contains information useful for
start-ups and troubleshooting. If the down/up arrow key is pressed continuously, every 0.5
seconds the next/previous item will be displayed.

As illustrated above, the monitor displays

MONITOR #1

,

LOAD CURRENT

,

INPUT VOLTAGE

,

and

OUTPUT VOLTAGE

as default. The four variables displayed in these monitor windows are

programmable via Items 289-292 (see page 8-30).

Terminals "S6", "S7", and "S8" exist on option boards INV3-COM-B and INV3-COM-D. Terminal
"OUT" is an output contact available on option boards INV3-COM-B and INV3-COM-D. "MC" is
the soft start resistor bypass contactor (should always show "ON").

Monitor currents can be shown in amps by adjusting Item 296,

CURRENT UNITS SELECTION

to

"1". Monitor voltages can be shown in percent by adjusting Item 297,

VOLTAGE UNITS

SELECTION

to "0".

The monitor's past four faults can be cleared by setting Item 280,

STANDARD SETTING MODE

SELECTION

to "4".

7 - 3

Keystroke

Display

Explanation

OUTPUT FREQUENCY

Standard output frequency display

0.0Hz

MON

MOTOR RUN DIRECTION:

Pressing the MON key places drive in monitor

FORWARD

mode. The first monitor window indicates direction.

down arrow

MONITOR #1

Programmable monitor #1

0.0 Hz

(the default shows frequency command)

down arrow

LOAD CURRENT

Programmable monitor #2

0%

(default setting shows total current in percent)

down arrow

INPUT VOLTAGE

Programmable monitor #3

228V

(default setting shows input voltage)

down arrow

OUTPUT VOLTAGE

Programmable monitor #4

0V

(default setting shows output voltage)

down arrow

STATUS:

R:--

S1:ON

Input terminal monitor. Drive displays "ON"

S2:--

S3:ON

S4:--

when terminal is shorted to "CC".

down arrow

ST:ON

F:--

RES:ON

Input terminal monitor. Drive displays "ON"

S5:--

S6:ON

S7:--

when terminal is shorted to "CC".

down arrow

RCH:ON

LOW:ON

FL:ON

Output contact monitor. Drive displays "ON" when

OUT:ON

FAN:--

MC:ON

output is energized.

down arrow

CUMULATIVE RUN TIME

Non-resettable run time monitor. ".01" = 1 hour.

0.00

down arrow

PAST TRIP #1

Past trip #1 monitor

OVERCURRENT (ACCEL)

down arrow

PAST TRIP #2

Past trip #2 monitor

OVERCURRENT (DECEL)

down arrow

PAST TRIP #3

Past trip #3 monitor

OVERVOLTAGE (DECEL)

down arrow

PAST TRIP #4

Past trip #4 monitor

NO ERROR

down arrow

MOTOR RUN DIRECTION:

Return to the first monitor window

FORWARD