Toshiba, Group:protection parameters – Toshiba Adjustable Speed Drive H3 User Manual
Page 49
TOSHIBA
REGENERATION POWER
155
allows drive to use regen
0: Off
-
0
9-17
RIDE-THROUGH
for control power
1: On *
REGENERATION RIDE
-
156*
maximum allowable
0.0 - 25
0.1 sec
2.0
9-17
THROUGH TIME
ride-through time
AUTO-RESTART (MOTOR
157
"catch" a spinning motor
0: Off
-
0
9-17
SPEED SEARCH)
(forward or reverse)
1: After momentary
power failure
(ride-through)
2: After "ST" is
shorted to "CC"
3: Both 1 and 2
ELECTRONIC THERMAL
158
sets drive's overload to
10-100% or amps
1%/A
100
9-18
PROTECT LVL 1
protect motor
OVERLOAD REDUCTION
159
frequency at which drive's motor
0 - 30
0.1/0.01 Hz
30.0
9-18
START FREQ
overload becomes speed sensitive
MOTOR 150% OVERLOAD
160
sets motor overload time
10 - 2400
10 sec
600
9-18
TIME LIMIT
OVERLOAD SELECTION
161
OL selection
0: Standard
-
0
9-18
1: Soft stall on
2: Motor OL trip off
3: Soft stall on,
Motor OL trip off
STALL PROTECTION
162
Stall protection #1
0: On **
-
0
9-18
ENABLE
1: Off
STALL PROTECTION
163**
sets current limit
10 - 215%/A
1 %/A
120
9-18
CURRENT LEVEL
UNDERVOLTAGE TRIP
164
Undervoltage detection can
0: Trip disabled
-
0
9-18
SELECTION
cause a warning or a trip
1: Trip enabled
UNDERVOLTAGE DETECT
165
Undervoltage detection time
0 - 10
0.01 sec
0.03
9-18
TIME
LOW CURRENT DETECT
166
Low current detection can
0: Trip disabled
-
0
9-18
SELECTION
cause a warning or a trip
1: Trip enabled
LOW CURRENT DETECT
167
Low current detection level
0 - 100% or amps
1%/A
0
9-19
LEVEL
LOW CURRENT
168
Low current detection time
0 - 255
1 sec
0
9-19
DETECTION TIME
OUTPUT SHORT-CIRCUIT
169
Output short-circuit detection
0: Standard
-
0
9-19
DETECTION SELECT
selection (OCL)
1: Less sensitive
short-circuit checki
2: Short-circuit check
at power up only
3: Combination of
1 and 2 above
8 - 14
GROUP:PROTECTION PARAMETERS
(cont'd)
PARAMETER
DESCRIPTION
LIQUID CRYSTAL DISPLAY
ADJUSTMENT
RANGE
ITEM
NO.
PAGE
NO.
DISPLAY
RESOLUTION
FACTORY
SETTING
Table continued on next page
*Item 156 is available only when Item 155 Adjustment Range option 1 is selected.
**Item 163 is available only when Item 162 Adjustment Range option 0 is selected.
Specifications
Precautions
Wiring
Jumpers
Panel
Keypad
Parameters
Programming
Service
Dimensions
Index
Inspection