TOSHIBA

9 - 11

Parameter Explanations (cont'd)

Output Contacts' Functions

Value

Comments

0

Contact will close when drive is at or above Item 7,

LOWER LIMIT FREQUENCY

1

Contact will close when drive is not at or above

LOWER LIMIT FREQUENCY

2

Contacts will close when drive is at Item 6,

UPPER LIMIT FREQUENCY

3

Contacts will close when drive is not at

UPPER LIMIT FREQUENCY

4

Default for LOWA/LOWC terminals. Contact will close when drive is at or above speed in

Item 72,

LOW SPEED SIGNAL OUTPUT FREQUENCY

5

Contact will close when drive is not at or above

LOW SPEED SIGNAL OUTPUT FREQUENCY

6

Default for RCHA/RCHC terminals. Contact closes when any accel or decel is complete.

7

Contact closes when any acceleration or deceleration is not complete.

8

Contact closes when drive is at or above Item 74,

SPEED REACH MAXIMUM FREQUENCY

during an accel or when drive is at or above Item 75,

SPEED REACH MINIMUM FREQUENCY

during a decel

9

Contact closes when drive is not at or above

SPEED REACH MAXIMUM FREQUENCY

during an

accel or when drive is not at or above

SPEED REACH MINIMUM FREQUENCY

during a decel.

10

Default for FLA/FLB/FLC terminals. Contact closes when drive is faulted (ESTOP is not a fault)

11

Contact closes when drive is not faulted (ESTOP is not a fault)

12

Contact closes when drive is faulted on anything except

EARTH FAULT

or

LOAD END

OVERCURRENT

(ESTOP is not a fault)

13

Contact closes when drive is faulted on

EARTH FAULT

or

LOAD END OVERCURRENT

14

Contact closes when overcurrent stall is active (use as overcurrent pre-alarm). The stall current

level is adjustable via Item 163 or Item 20 (see).

15

Contact closes when overcurrent stall is not active. The stall current level is adjustable via Item

163 or Item 20 (see).

16

Contact closes to signify drive overload pre-alarm. Example of drive overload: H3 is rated

for 150% of rated current for 2 minutes. If drive is operated at 150% of rated current for one

minute, the drive overload is at 50%, or half of its overload current-time capability. The drive

trips on overload at 100%. Drive overload pre-alarm starts at 50%.

17

Contact closes to signify drive is not in an overload pre-alarm. See explanation for value 16

above.

18

Contact closes to signify motor overload pre-alarm. Example of overload: H3 is rated for 150%

of rated current for 2 minutes. If drive is operated at 150% of rated current for one minute, the

drive overload is at 50%, or half of its overload current-time capability. The drive trips on

overload at 100%. Overload pre-alarm starts at 50%.

19

Contact closes to signify motor is not in an overload pre-alarm. See explanation for value 18

above.

20

Contact closes when heatsink reaches 84

O

C. Contact opens at 80

O

C after it has closed

21

Contact closes when heatsink is under 84

O

C. Contact closes at 80

O

C after it has opened

22

Contact closes when drive is displaying

OVERVOLTAGE

. See page 10-7.

23

Contact closes when drive is not displaying

OVERVOLTAGE

. See page 10-7.

24

Contact closes when drive is displaying

DC BUS UNDERVOLTAGE

. See page 10-7.

25

Contact closes when is not displaying

DC BUS UNDERVOLTAGE

. See page 10-7.

26

Contact closes when output current is at or greater than the current programmed into Item 167,

LOW CURRENT DETECTION LEVEL

for longer than the time programmed in Item 168,

LOW

CURRENT DETECTION TIME

27

Contact closes when output current is not at or greater than the current programmed into

LOW

CURRENT DETECTION LEVEL

for longer than the time programmed in

LOW CURRENT

DETECTION TIME

28

Contact closes when torque current equals or exceeds the setting programmed into Item 171,

OVERTORQUE TRIP LEVEL

29

Contact closes when torque current does not equal or exceed the setting programmed into

OVERTORQUE TRIP LEVEL