Toshiba, Group:protection parameters – Toshiba Adjustable Speed Drive H3 User Manual

Page 50

background image

TOSHIBA

OVERTORQUE TRIP

170

Overtorque detection can cause

0: Trip disabled

-

0

9-19

SELECTION

a warning or a trip

1: Trip enabled

OVERTORQUE TRIP

171

Overtorque trip level

10-200% or amps

1%/A

150

9-19

LEVEL

FAULT TRIP EEPROM

172

Fault trip saving

0: Fault

-

0

9-19

SAVE ENABLE

cleared when
power cycled

1: Fault display

retained when
power cycled*

COOLING FAN CONTROL

173

Cooling fan control selection

0: Automatic fan

-

0

9-19

SELECTION

1: Fan always on

CUMULATIVE RUN TIMER

174

Cumulative run timer alarm setting

0.00 - 999.9

0.02

175.0

9-19

ALARM SETTING

(.01 = 1 hour)

8 - 15

GROUP:PROTECTION PARAMETERS

(cont'd)

PARAMETER

DESCRIPTION

LIQUID CRYSTAL DISPLAY

ADJUSTMENT

RANGE

ITEM

NO.

PAGE

NO.

DISPLAY

RESOLUTION

FACTORY

SETTING

*This parameter disables the retry function (see Items 153 and 154).