beautypg.com

Toshiba, Group:communication setting parameters – Toshiba Adjustable Speed Drive H3 User Manual

Page 59

background image

TOSHIBA

8 - 24

LIQUID CRYSTAL DISPLAY

ADJUSTMENT

RANGE

ITEM

NO.

PAGE

NO.

DISPLAY

RESOLUTION

FACTORY

SETTING

PARAMETER

DESCRIPTION

GROUP:COMMUNICATION SETTING PARAMETERS

Cycle power after changing any parameter in

GROUP: COMMUNICATION SETTING PARAMETERS

.

Table continued on next page

*Items 265 - 266 are available only when Item 264 Adjustment Range option 1 is selected.
**Item 267 is available only when Item 264 Adjustment Range option 2 or 3 is selected.

RS232 BAUD RATE

260

set RS232 baud rate

0: 2400 baud

-

2

9-22

1: 4800 baud
2: 9600 baud

NUMBER OF DATA BITS

261

Number of data bits

0: 7 bits

-

0

9-22

1: 8 bits

PARITY SETTING

262

Parity

0: Even parity

-

0

9-22

1: Odd parity

INVERTER ID NUMBER

263

Inverter number

0 - 255

-

0

9-22

COMMUNICATION

264

Communication selection

0: Off

-

0

9-23

SELECTION

1: RS485 board*
2: Tosline-F10,
DN board,
MB+ board,

RIO board**

3: Tosline-S20 **
4: 12-bit binary input

(option board)

5: BCD board

(0.1 Hz units)

6: BCD board

(1 Hz units)

MASTER/SLAVE

265*

Master/follower selection

0: Follower

-

0

9-23

SELECTION

1: Master (follower

follows master
freq. command)

2: Master (output

frequency)

RS485 BAUD RATE

266*

RS485 baud rate

0: Normal mode

-

0

9-23

1: High speed mode

TOSLINE-F10/S20

267**

TOSLINE-F10/TOSLINE-S20

0: Off

-

0

9-23

COMMAND INPUT

command input

1: Frequency

command

2: Command input
3: Frequency

command,
command input

Specifications

Precautions

Wiring

Jumpers

Panel

Keypad

Parameters

Programming

Service

Dimensions

Index

Inspection