beautypg.com

Toshiba, Group:fundamental parameters #1 – Toshiba Adjustable Speed Drive H3 User Manual

Page 36

background image

TOSHIBA

8 - 1

*Item 9 is available only when Item 8 Adjustment Range option 1 or 2 is selected.

GROUP:FUNDAMENTAL PARAMETERS #1

PARAMETER

DESCRIPTION

LIQUID CRYSTAL DISPLAY

ADJUSTMENT

RANGE

ITEM

NO.

PAGE

NO.

DISPLAY

RESOLUTION

FACTORY

SETTING

MAXIMUM OUTPUT

1

Maximum frequency

30 - 400 Hz

0.01/0.1 Hz

80 Hz

9-3

FREQUENCY

BASE FREQUENCY #1

2

Base frequency #1

25 - 400 Hz

0.01/0.1 Hz

60 Hz

9-3

BASE FREQUENCY

3

Base frequency voltage selection

0: Input voltage level

-

1

9-3

VOLTAGE SELECT

1: Automatic setting
2: Stationary setting

MAXIMUM OUTPUT

4

Maximum voltage #1 for 230V

0 - 255V

1V

230V

9-3

VOLTAGE #1

Maximum voltage #1 for 460V

0 - 510V

1V

460V

9-3

REVERSE OPERATION

5

Reverse operation disable selection 0: Reverse allowed

-

0

9-3

DISABLE SELECT

1: Reverse not

allowed

UPPER LIMIT

6

Upper limit frequency

0.0 Hz - Maximum 0.01/0.1 Hz

80.0

9-3

FREQUENCY

Output Frequency

LOWER LIMIT

7

Lower limit frequency

0.0 Hz - Upper

0.01/0.1 Hz

0.0

9-3

FREQUENCY

Limit Frequency

VOLTS PER HERTZ

8

V/F pattern

1: Constant torque *

-

1

9-3

PATTERN

2: Variable torque *
3: Automatic torque

boost

4: Automatic torque

boost with
automatic energy
savings feature

5: Vector control
6: Vector control with

automatic energy
savings feature

VOLTAGE BOOST #1

9 *

30 HP and less

0 - 30%

0.1%

3%

9-4

40 HP and greater

1%

ACCELERATION TIME #1

10

60 HP and less

0.1-6000/0.01-600.0

0.1s/0.01s

10 sec

9-4

75 HP and greater

60 sec

DECELERATION TIME #1

11

60 HP and less

0.1-6000/0.01-600.0

0.1s/0.01s

10 sec

9-4

75 HP and greater

60 sec

ACC/DEC PATTERN #1

12

Acc/Dec pattern #1

0: Linear

-

0

9-4

SELECTION

1: Self-adjusting
2: S-Pattern
3: Overspeed Pattern

ACCEL/DECEL PATTERN

13

Acc/Dec pattern adjustment

0 - 50

1%

25

9-5

ADJUST LOW

amounts (low)

ACCEL/DECEL PATTERN

14

Acc/Dec pattern adjustment

0 - 50

1%

25

9-5

ADJUST HIGH

amounts (high)

SECTION 8: Programming Charts