beautypg.com

Toshiba, Group:frequency setting parameters – Toshiba Adjustable Speed Drive H3 User Manual

Page 43

background image

TOSHIBA

8 - 8

GROUP:FREQUENCY SETTING PARAMETERS

PARAMETER

DESCRIPTION

LIQUID CRYSTAL DISPLAY

ADJUSTMENT

RANGE

ITEM

NO.

PAGE

NO.

DISPLAY

RESOLUTION

FACTORY

SETTING

Table continued on next page

*Items 84 - 87 are available only when Item 83 Adjustment Range option 1 is selected.

**Items 89 - 92 are available only when Item 88 Adjustment Range option 1 is selected.
***Items 94 - 97 are available only when Item 93 Adjustment Range option 1 is selected.

FREQUENCY PRIORITY

80

Assign priority to frequency

1:RR terminal

-

1

9-13

SELECTION #1

reference sources

2:IV terminal
3:RX terminal
4:PG input
5:Binary input or MOP

FREQUENCY PRIORITY

81

Assign second priority

1:RR terminal

2

9-13

SELECTION #2

frequency reference source

2:IV terminal
3:RX terminal
4:PG input
5:Binary input or MOP

ANALOG INPUT FILTER

82

Analog input filter

0 - 3

-

0

9-14

RR TERMINAL STANDARD

83

RR input selection

0: Standard

-

0

9-14

OR ADJUSTABLE

1: Adjustable *

5-1

RR REFERENCE SETTING

84*

RR reference point #1

0 - 100%

1%

0

9-14

POINT #1

of terminal max (10V)

RR REF POINT #1

85*

Output frequency desired

0 - Max. Out. Freq.

0.1/0.01 Hz

0.0

9-14

FREQUENCY

with input entered in Item 84

RR REFERENCE SETTING

86*

RR reference point #2

0 - 100%

1%

100

9-14

POINT #2

of terminal max (10V)

RR REF POINT #2

87*

Output frequency desired

0 - Max.Out. Freq.

0.1/0.01 Hz

80.0

9-14

FREQUENCY

with input entered in Item 86

IV TERMINAL STANDARD

88

IV input selection

0: Standard

-

0

9-14

OR ADJUSTABLE

1: Adjustable **

5-1

IV REFERENCE SETTING

89**

IV reference point #1

0 - 100%

1%

20

9-14

POINT #1

of terminal maximum

IV REF POINT #1

90**

Output frequency desired

0 - Max. Out. Freq.

0.1/0.01 Hz

0.0

9-14

FREQUENCY

with input entered inItem 89

IV REFERENCE SETTING

91**

IV reference point #2

0 - 100%

1%

100

9-14

POINT #2

of terminal maximum

IV REF POINT #2

92**

Output frequency desired

0 - Max. Out. Freq.

0.1/0.01 Hz

80.0

9-14

FREQUENCY

with input entered in Item 91

RX TERMINAL STANDARD

93

RX input selection

0: Standard

-

0

9-14

OR ADJUSTABLE

1: Adjustable ***

5-1

RX REFERENCE SETTING

94***

RX reference point #1

-100 - 100%

1%

0

9-14

POINT #1

of terminal maximum

RX REF POINT #1

95***

Output Hz desired with input

-Max. Out. Freq. to

0.1/0.01 Hz

0.0

9-14

FREQUENCY

entered in Item 94

Max. Out. Freq.

RX REFERENCE SETTING

96***

RX reference point #2

-100 - 100%

1%

100

9-14

POINT #2

of terminal maximum

RX REF POINT #2

97***

Output Hz desired with input

-Max. Out. Freq. to

0.1/0.01 Hz

80.0

9-14

FREQUENCY

entered in Item 96

Max. Out. Freq.

Specifications

Precautions

Wiring

Jumpers

Panel

Keypad

Parameters

Programming

Service

Dimensions

Index

Inspection