Toshiba, Group:fundamental parameters #2 – Toshiba Adjustable Speed Drive H3 User Manual
Page 37
TOSHIBA
BASE FREQUENCY #2
15
Base frequency #2
25 - 400 Hz
0.01/0.1 Hz
60.0
9-5
MAXIMUM OUTPUT
16
Maximum voltage #2 for 230V
0 - 255V
1V
230V
9-5
VOLTAGE #2
Maximum voltage #2 for 460V
0 - 510V
1V
460V
9-5
VOLTAGE BOOST #2
17 *
30 HP and less
0 - 30%
0.1%
3%
9-5
40 HP and greater
1%
ELECTRONIC THERMAL
18
Electronic thermal protection
10-100% or amps
1%/A
100
9-5
PROTECT LVL #2
level #2
STALL PROTECTION
19
turn stall #2 on/off
0: On **
-
0
9-5
SELECTION #2
1: Off
STALL PROTECTION
20**
adjust stall current level #2
10-215% or amps
1%/A
120%
9-5
LEVEL #2
ACCELERATION TIME #2
21
60 HP and less
0.1-6000/0.01-600.0
0.1s/0.01s
10 sec
9-5
75 HP and greater
60 sec
DECELERATION TIME #2
22
60 HP and less
0.1-6000/0.01-600.0
0.1s/0.01s
10 sec
9-5
75 HP and greater
60 sec
ACC/DEC PATTERN #2
23
Acc/Dec pattern #2
0: Linear
-
0
9-5
SELECTION
1: Self-adjusting
2: S-Pattern
3: Overspeed Pattern
ACC/DEC #1/#2 SWITCH
24
Hz at which to switch from
0 - Max. Output Freq. 0.1/0.01 Hz
0.0
9-5
FREQUENCY
ACC1/DEC1 to ACC2/DEC2
(Item 1)
8 - 2
GROUP:FUNDAMENTAL PARAMETERS #2
PARAMETER
DESCRIPTION
LIQUID CRYSTAL DISPLAY
ADJUSTMENT
RANGE
ITEM
NO.
PAGE
NO.
DISPLAY
RESOLUTION
FACTORY
SETTING
*Item 17 is available only when Item 8,
VOLTS PER HERTZ PATTERN
Adjustment Range option 1 or 2
is selected.
**Item 20 is available only when Item 19 Adjustment Range option 0 is selected.
Specifications
Precautions
Wiring
Jumpers
Panel
Keypad
Parameters
Programming
Service
Dimensions
Index
Inspection