beautypg.com

3 rs485 interface, User interface – KACO Powador XP500-XP550-HV TL User Manual

Page 93

background image

Operating Instructions Powador XP500/550-HV-TL

Page 93

User interface

9.3 RS485 interface

The inverter has two RS485 connections.
RS485-1

Interface for the Powador Argus
Interface for optional Powador-go

RS485-2

Interface for the MMI’s internal data logger, or for the external Powador proLOG data logger

9.3.1 RS485-1 Interface

1d

5d

2d

6d

3d

7d

4d

8d

1c

PE

5c

2c

6c

3c

7c

4c

8c

1c

PE

1d

PE

RS485

2d

5d

2c

5c

3d

6d

3c

6c

4d

7d

8d

4c

7c

8c

Signal transceiver

A

B

GND

Figure 82: RS485-1 connection

Figure 83: Circuit diagram for RS485-1

connection

Terminal number

Terminal designation

Specification

Wire cross- section

1c

RS485 A1

RS485 signal A1

AWG 20

(0.518mm

2

)

1d

RS485 B1

RS485 signal B1

3c

RS485 C1

Termination resistor
terminal

3d

RS485 G1

RS485 data transmission
GND 1

"

For termination disposal, you can use RS485 B1(1d) and RS485 C1(3c) with jumper because termination
resistor is already installed inside of XCU of XP500/550-HV-TL.

Table 26: Connections for RS485-1