Operating Instructions Powador XP500/550-HV-TL

Parameters

Parameters

Min

Max

Unit

Descriptions

MPPT V Minimum

200

800

V

dc

Minimum voltage to run MPPT
Exception)

DC Over Voltage
Level

300

1020

V

dc

Upper limit for PV over voltage fault

DC Over Current
Level

0

150

%

Upper limit for PV over current fault

MPP Factor

0

1

-

Maximum power point factor

MPP Range Upper

10

300

V

dc

Upper limit of maximum power point

MPP Range Lower

10

300

V

dc

Lower limit of maximum power point

PV Operation Level 900

1020

V

dc

Maximum PV operation level

Table 12: PV Array Parameters

8.1.1 Operating DC voltage range

Figure 47: Operating DC voltage range

The range of possible operational input voltage is from [MPPT V Minimum] to [PV Operation Level]. The picture
above shows that the output power decreases linearly where the input power is from [MPPT V Maximum] to
[PV Operation Level].