6faults and warnings, 1 warning – KACO Powador XP500-XP550-HV TL User Manual
Page 45
Operating Instructions Powador XP500/550-HV-TL
Page 45
Faults and Warnings
6
Faults and Warnings
When a problem occurs in the system, the Inverter will beep and inform the user on the GUI. The Inverter dis-
plays two basic error messages. The first, the fault, is a serious problem that causes the inverter to stop running.
The second, a warning, is a minor problem that does not cease the system operation. The GUI will indicate
faults in red and warnings in yellow. The user can find a description of the different fault and warnings in the
following Tables.
6.1 Warning
Message
Code
Description
SP1(PV SP) Failure
81
Failure of the PV side surge protector(SP1)
CB10(PV Contactor) Failure 82
PV side contactor(CB10) failure
PV Fuse Failure
83
PV side Fuse failure(option)
Ground Fault Warning
84
The insulation resistance of the PV falls short of the limit set in the
ground fault monitoring for Alert1(option)
PV Over Voltage
85
PV voltage exceeds the parameter [DC over voltage Level]
PEBB Over Temp. Warning 100
The temperature of the PEBB(Power Electronics Building Block) over
85°C(185°F)
PEBB Fan Failure
101
Failure of a PEBB(Power Electronics Building Block) fan
PEBB Temperature
Unbalance
102
The Difference of each PEBB temperature exceeds the operational
parameter [PEBB Temperature Unbalance Level]
SP2(Grid SP) Failure
110
Failure of the grid side surge protector(SP2)
ASYNC Warning
111
The phase synchronous of inverter and grid failure
Test Mode
120
The system is working in test mode
Watchdog
121
Abnormalities detection in the DSP
Invalid Parameter
125
Parameter is invalid value
Reconnection Condition
Warning
126
The grid voltage or frequency exceeds the reconnection condition
when reconnection to grid during operational parameter [Reconnec-
tion Condition Warning Delay] seconds
Cabinet Over Temp.
Warning
130
The temperature of the cabinet over the parameter [Cabinet Tempera-
ture Maximum]
Cabinet Under Temp.
Warning
131
The temperature of the cabinet falls below the parameter [Cabinet
Temperature Minimum]
SP3(Control Power SP)
Failure
132
Failure of the control side surge protector(SP3)
CB32 Open
133
Failure of the top fan or power supply
SMPS Warning
134
Failure of the control SMPS(Switching Mode Power Supply)
CAN TX Failure
135
CAN bus communication transmission failure
Table 7: Warning