Operating Instructions Powador XP500/550-HV-TL

Page 57

Maintenance/Cleaning

7.1

Maintenance intervals

DANGER

Lethal voltages are still present in the terminals and lines of the inverter even after the
inverter has been switched off and disconnected!
Coming into contact with the lines and terminals in the inverter will cause serious injury
or death.
Only authorized electricians who are approved by the supply grid operator may open,
install and maintain the inverter.

Do not touch the lines and terminals when switching the unit on and off. Do not touch
exposed contact connections.

Always shut down the inverter prior to cleaning or maintenance.

NOTE

Even between maintenance intervals, pay attention to any unusual behaviour that the inverter
displays during operation, and fix the problem immediately.

Recommended
Maintenance-inter-
vals

Maintenance work

6 months*

Cleaning or replacement

Filter mats in the air intake filter

6 months

Cleaning

Inside of the cabinet
Fans

12 months*

Function check

Emergency stop (OFF)

12 months

Cleaning

Power section of the heat sink

12 months

Visual inspection

Contact connection
Fuses
Switches
Overvoltage protection
Redundant auxiliary power supplies
Check all parts in the cabinet for

Heavy dust deposits and soiling

Moisture (especially water that has
permeated from the outside)

Visual inspection
(and replacement, if necessary)

All warning labels

Function check

Fans
Door contacts
Operating lights and fault lights

12 months

Torque check

Input, output, Check the status of the screws

*If heavy soiling is present at the installation location, you may need to shorten the maintenance interval.

Table 11: Maintenance intervals