beautypg.com

KACO Powador XP500-XP550-HV TL User Manual

Page 55

background image

Operating Instructions Powador XP500/550-HV-TL

Page 55

Faults and Warnings

Code Message

Warning Description

Possible problem and Solution(s)

52

Master Slave Fault

Master Slave operation Failure

Possible problem
• Wrong CAN ID
• CAN bus communication Failure
Solution(s)
• Check the parameters
• Check the CAN bus Connection
• Check the CAN bus terminal registers

57

Grid Over Frequency
Level 3

Grid side Frequency over the
parameter [Grid Over Frequency
Level 3]

Possible problem
• The grid frequency is outside the
permitted range
Solution(s)
• Check the grid frequency
• Check the grid parameter

58

Grid Under Frequency
Level 3

Grid side Frequency under the
parameter [Grid Under Fre-
quency Level 3]

Possible problem
• The grid frequency is outside the
operation range
Solution(s)
• Check the grid frequency
• Check the grid parameter

63

MMI-XCU Communi-
cation Error

MMI-XCU communication Error Possible problem

• MMI-XCU Communication Error
Solution(s)
• Check MMI-XCU communication
connectivity

Table 10: Fault