Operating Instructions Powador XP500/550-HV-TL

Parameters

8.7.8 Operation Mode

COSPHI Control operates in RPC (Remote Power Control) and internal modes according to communication
status to control power with Fixed COSPHI and Fixed Q.

Figure 63: Transition of RPC mode and Internal Mode

1. RPC mode

While MMI is modifying XCU’s {Remote Power Control}, {COSPHI RPC Reactive Power} and {COSPHI RPC

Power Factor} parameters with two-minute interval, COSPHI Control operates in RPC mode. In RPC mode,

it operates according to {Remote Power Control}, {COSPHI RPC Reactive Power}, and {COSPHI RPC Power

Factor} modes.

2. Internal mode

If RPC mode parameter such as {Remote Power Control}, {COSPHI RPC Reactive Power}, and {COSPHI RPC

Power Factor} is not be modified within five minutes, XCU will operate in Internal mode. In Internal mode,

COSPHI control operates according to internal mode parameters such as {COSPHI Internal Reactive Power}

and {COSPHI Internal Power Factor}, {Remote Power Control} parameter does not influence on the active

power.

Figure 64: PQ Diagram of XP500-HV-TL