8 operation mode – KACO Powador XP500-XP550-HV TL User Manual
Page 82
Page 82
Operating Instructions Powador XP500/550-HV-TL
Parameters
8.7.8 Operation Mode
COSPHI Control operates in RPC (Remote Power Control) and internal modes according to communication
status to control power with Fixed COSPHI and Fixed Q.
Figure 63: Transition of RPC mode and Internal Mode
1. RPC mode
While MMI is modifying XCU’s {Remote Power Control}, {COSPHI RPC Reactive Power} and {COSPHI RPC
Power Factor} parameters with two-minute interval, COSPHI Control operates in RPC mode. In RPC mode,
it operates according to {Remote Power Control}, {COSPHI RPC Reactive Power}, and {COSPHI RPC Power
Factor} modes.
2. Internal mode
If RPC mode parameter such as {Remote Power Control}, {COSPHI RPC Reactive Power}, and {COSPHI RPC
Power Factor} is not be modified within five minutes, XCU will operate in Internal mode. In Internal mode,
COSPHI control operates according to internal mode parameters such as {COSPHI Internal Reactive Power}
and {COSPHI Internal Power Factor}, {Remote Power Control} parameter does not influence on the active
power.
Figure 64: PQ Diagram of XP500-HV-TL