KACO Powador XP500-XP550-HV TL User Manual
Page 64
Page 64
Operating Instructions Powador XP500/550-HV-TL
Parameters
Parameters
Min
Max
Unit
Descriptions
Reconnection
Condition Check
Time Normal
0
1800
sec
This parameter is used for time check during
“Reconnection condition” for all the time except
after fault.
Reconnection
Condition Check
Time After Fault
0
1800
sec
This parameter is used for time check during
“Reconnection condition” for after fault only.
Grid Over Frequency
Level 3
0
3
Hz
Upper limit for grid over frequency level 3
Grid Over Frequency
Level 3 Trip Time
40
2000
ms
Time for grid over frequency Level 3 trip
Grid Over Voltage
Level Slow
105
115
%
This parameter represents Upper limit for the
average RMS value of grid voltage as a percentage
of the rated grid voltage.
If the average RMS value of grid voltage exceeds
this parameter setting, fault will be occurred.
VDE-AR-N 4105(Germany Low Voltage Require-
ments)
Grid Over Voltage
Level Slow Shift
Average Time
-1
3000
sec
This parameter determines how long the average
RMS value of grid voltage will be calculated.
(Low Voltage Requirements: 600 seconds duration)
Negative value means that the relevant function
(Grid Over Voltage level slow) is disabled.
Reconnection
Condition Warning
Delay
0
600
sec
Time delay for Reconnection Condition Warning
Grid Under Fre-
quency Level 3
0
3
Hz
Lower limit for grid over frequency level 3
Grid Under Fre-
quency Level 3 Trip
Time
0
60000
ms
Time for grid over frequency Level 3 trip
Upper Deadband
PPN
100
110
%
Voltage Level for activation of P/Pn function when
selected CEI 0-21 grid code
Lower Deadband
PPN
90
100
%
Voltage Level for deactivation of P/Pn function
when selected CEI 0-21 grid code
Upper Deadband
QV
10
100
%
Active Power Level for activation of Q(V) function
when selected CEI 0-21 grid code
Lower Deadband
QV
1
20
%
Active Power Level for deactivation of Q(V)
function when selected CEI 0-21 grid code
QV Voltage 1
100
110
%
Voltage upper dead band of Q(V) function when
selected CEI 0-21 grid code
QV Voltage 2
90
100
%
Voltage lower dead band of Q(V) function when
selected CEI 0-21 grid code
Table 14: Grid Parameters