Operating Instructions Powador XP500/550-HV-TL

Page 79

Parameters

8.7.4 Conceptual Relation between Output Power and Temperature

Below graph represents conceptual relation between inverter output power and heat sink temperature. The
output power is reduced in proportion to heat sink temperature but keep in mind that the power derating is
activated at 90°C and deactivated at 70°C (The activation/deactivation temperature can be tunable by param-
eter).

Figure 60: Relation between output power and temperature

8.7.5 COSPHI Control

COSPHI Control function is for controlling active and reactive power which is infused from XP inverter to the
grid with Prolog, MMI, and XCU at long distance.

Figure 61: COSPHI Control composition