Operating Instructions Powador XP500/550-HV-TL

Page 17

Storage/Installation/Start-up

(1)

(2)

Figure 6: Transporting the unit at the installation location

5.3 Selecting the installation location

NOTE

The maximum flow rate of the cooling air is 6940m³ per hour.
Please keep this value in mind when you select the installation location.

Floor

Must have adequate load-bearing capacity

The building material must meet the requirements of building material class B1 (“Flame-resistant Building
Materials”, in accordance with DIN EN 13501-1)

Room

Should be as dry as possible

Must be indoors (IP21)

The installation location must be climate-controlled in order to dissipate the waste heat

Additional ventilation should be provided, if necessary

Do not install in a room where there is a risk of explosion

Clearance between walls and ceiling

Must be accessible for installation and maintenance

Air circulation may not be blocked

You do not have to provide for clearance on the sides or to the rear of the unit

Minimum clearance between unit and ceiling 60cm