Operating Instructions Powador XP500/550-HV-TL

Parameters

Grid Over Frequency

Figure 49: Grid over frequency

1. f > f

rated

+0.2Hz, t > 100ms → Grid Over Frequency Fault

2. It disables Grid Over Frequency Level 2 and Grid Over Frequency Level 2.

Grid Under Voltage

Figure 50: Grid under voltage

1. U < 0.9*U

rated

, t > 5s → Grid Under Voltage Level 1 Fault

2. U < 0.8*U

rated

, t > 100ms → Grid Under Voltage Level 2 Fault