Operating Instructions Powador XP500/550-HV-TL
Page 67
Parameters
Grid Over Voltage
Figure 51: Grid over voltage
1. U > 1.1*U
rated
, t > 5s → Grid Over Voltage Level 1 Fault
2. U > 1.2*U
rated
, t > 100ms → Grid Over Voltage Level 2 Fault
8.3.2 FRT Enable On
The parameter when FRT Enable is on is as follows.
Parameters
Min
Max
Unit
Descriptions
FRT Enable
0
1
-
FRT(Fault Ride Through) Function
0: Disable
1: Enable
Grid Under Voltage
Level 2
15
100
%
Lower limit expressed as a percentage of the
rated grid voltage for grid under voltage Level 2
Grid Under Voltage
Level 1 Trip Time
100
10000
ms
Time for grid under voltage level 1 trip
Grid Under Voltage
Level 2 Trip Time
40
3000
ms
Time for grid under voltage level 2 trip
MPP Range Upper
10
300
V
dc
Upper limit of maximum power point
MPP Range Lower
10
300
V
dc
Lower limit of maximum power point
Table 15: FRT Enable On