beautypg.com

KACO Powador XP500-XP550-HV TL User Manual

Page 63

background image

Operating Instructions Powador XP500/550-HV-TL

Page 63

Parameters

Parameters

Min

Max

Unit

Descriptions

Grid Over Voltage
FRT Enable

0

1

Over Voltage FRT Function
0: Disable
1: Enable

Power Reduction
Gradient Level

0

100

%/Hz

Gradient level for frequency dependant power
reduction

Power Reduction
Deactivation
Frequency

0

0.3

Hz

Frequency limit for frequency dependant power
reduction deactivation

Grid Over Frequency
Level 2

0

3

Hz

Upper limit for grid over frequency level 2

Grid Over Frequency
Level 2 Trip Time

40

2000

ms

Time for grid over frequency Level 2 trip

Reconnection
Condition Mode

0

2

-

Reconnection Condition Function
0: Disable
1: Checked before connected to grid (Germany
Medium Voltage Requirements)
2: Checked according to VDE-AR-N 4105 (Germany
Low Voltage Requirements)

Reconnection
Condition Upper
Voltage

-1

130

%

This parameter represents the upper voltage in the
range of “Reconnection condition” as a percent-
age of the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Reconnection
Condition Lower
Voltage

-1

100

%

This parameter determines the lower voltage of
“Reconnection condition” range as a percentage
of the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Reconnection
Condition Upper
Frequency

-1

3

Hz

This parameter determines the upper frequency of
“Reconnection condition” range as an increment
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Reconnection
Condition Lower
Frequency

-1

3

Hz

This parameter determines the lower frequency of
“Reconnection condition” range as a decrement
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Table 14: Grid Parameters