2 overview of operating states – KACO Powador XP500-XP550-HV TL User Manual
Page 30
Page 30
Operating Instructions Powador XP500/550-HV-TL
Storage/Installation/Start-up
5.6.2 Overview of operating states
Figure 16: Overview of operating states
Tag
Parameter
Default Value
T
Shift
Time Shift (Grid tab)
0 sec
V
pv_start
MPPT V Start (PV Array tab)
600V (above 500kVA: 700V)
T
start
MPPT T Start (PV Array tab)
HV model: 300 sec, TL model: 900 sec
V
mpp_min
MPPT V Minimum (PV Array tab)
410V (above 500kVA capacity: 505V)
P
stop
MPPT P Stop (PV Array tab)
10kW (below 100kVA capacity: 1kW)
T
stop
MPPT T Stop (PV Array tab)
HV model: 30 sec, TL model: 60 sec
Table 4: Parameters of operating states