2 overview of operating states – KACO Powador XP500-XP550-HV TL User Manual

Page 30

background image

Page 30

Operating Instructions Powador XP500/550-HV-TL

Storage/Installation/Start-up

5.6.2 Overview of operating states

Figure 16: Overview of operating states

Tag

Parameter

Default Value

T

Shift

Time Shift (Grid tab)

0 sec

V

pv_start

MPPT V Start (PV Array tab)

600V (above 500kVA: 700V)

T

start

MPPT T Start (PV Array tab)

HV model: 300 sec, TL model: 900 sec

V

mpp_min

MPPT V Minimum (PV Array tab)

410V (above 500kVA capacity: 505V)

P

stop

MPPT P Stop (PV Array tab)

10kW (below 100kVA capacity: 1kW)

T

stop

MPPT T Stop (PV Array tab)

HV model: 30 sec, TL model: 60 sec

Table 4: Parameters of operating states