Operating Instructions Powador XP500/550-HV-TL

Faults and Warnings

Message

Code

Description

CAN RX Failure

136

CAN bus communication reception failure

CAN EP Failure

137

CAN bus communication Error-Passive error

CAN Bus-Off

138

CAN bus communication Bus-off error

CAN Wrong Message

139

Reception of Wrong message in CAN bus communication

CAN Time Out

140

Time out in CAN bus communication

CAN Multiple Master

141

There are multiple Masters in CAN bus communication

Table 7: Warning

6.2 Fault

Message

Code

Description

PV Over Voltage

1

PV voltage exceeds the parameter [DC over voltage Level]

PV Over Current

2

PV current exceeds the parameter [DC over current Level]

CB10(PV CB) Trip

4

PV side circuit breaker(CB10) tripped

PV Polarity Failure

5

Polarity(+, -) of PV side is reversed

Ground Fault

6

PV side ground fault

Inv. Over Voltage

10

Inverter side Voltage over the parameter [Grid Over Voltage Level 2]

Inv. Under Voltage

11

Inverter side Voltage under the parameter [Grid Under Voltage Level 2]

Inv. Over Frequency

12

Inverter side Frequency over the parameter [Grid over Frequency Level 2]

Inv. Under Frequency

13

Inverter side Frequency under the parameter [Grid under Frequency
Level 2]

Inv. Over Current

14

Inverter side Current over the parameter [Inverter OverCurrent Level]

MC21(Inv. MC) Failure

15

Inverter side contactor(MC21) failure

Inv. Phase Order

16

Phase order failure on the inverter side, wrong phase rotation

Inductor or TR Over Temp. 18

Inductor or Transformer temperature over 150°C

Inv. Current Unbalance

19

The unbalanced current of inverter side

PEBB(1) IGBT Fault

20

PEBB 1 IGBT failure

PEBB(2) IGBT Fault

21

PEBB 2 IGBT failure

PEBB(3) IGBT Fault

22

PEBB 3 IGBT failure

PEBB Over Temp. Analog

24

The temperature of the heat-sink over the parameter [Heatsink OT
Level] (Analog)

PEBB Over Temp. Digital

25

The temperature of the heat-sink over 100°C(Digital)

Grid Over Voltage 1

30

Grid side Voltage over the parameter [Grid Over Voltage Level 1]

Table 8: Fault