1 frt enable off – KACO Powador XP500-XP550-HV TL User Manual
Page 65
Operating Instructions Powador XP500/550-HV-TL
Page 65
Parameters
Parameters
Min
Max
Unit
Descriptions
QV Voltage 3
100
110
%
Voltage upper level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code
QV Voltage 4
90
100
%
Voltage lower level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code
QV Inductive Max
0
48
%
Reactive Power inductive maximum value of Q(V)
function
QV Capacitive Max 0
48
%
Reactive Power capacitive maximum value of Q(V)
function
Table 14: Grid Parameters
8.3.1 FRT Enable Off
If the function of FRT(Fault-ride through) is not active, XP series parameters for abnormal grid is as follows.
Grid Under Frequency
Figure 48: Grid under frequency
1. f < f
rated
–2Hz, t > 10s → Grid Under Frequency Level 1 Fault
2. f < f
rated
–2.5Hz, t > 100ms → Grid Under Frequency Level 2 Fault