Operating Instructions Powador XP500/550-HV-TL

Page 65

Parameters

Parameters

Min

Max

Unit

Descriptions

QV Voltage 3

100

110

%

Voltage upper level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code

QV Voltage 4

90

100

%

Voltage lower level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code

QV Inductive Max

0

48

%

Reactive Power inductive maximum value of Q(V)
function

QV Capacitive Max 0

48

%

Reactive Power capacitive maximum value of Q(V)
function

Table 14: Grid Parameters

8.3.1 FRT Enable Off

If the function of FRT(Fault-ride through) is not active, XP series parameters for abnormal grid is as follows.

Grid Under Frequency

Figure 48: Grid under frequency

1. f < f

rated

–2Hz, t > 10s → Grid Under Frequency Level 1 Fault

2. f < f

rated

–2.5Hz, t > 100ms → Grid Under Frequency Level 2 Fault